184
GROUP SETTING
ADDRESS
UNIT
001
002
REMOTE CONTROLLER
101
SYSTEM CONTROLLER
G01
15.1.3 Group configuration setting
●
Registration can be made for the indoor units, local remote controllers and slave system controllers in the same group.
●
Registration can also be performed for the group that is composed of only Lossnay.
Example of a group configuration
●
Supply the power from the power supply unit (PAC-SC34KUA) through the M-NET transmission cable.
●
Perform the following procedures to set the group configuration because the interlocked operation setting will not be per-
formed for the group configuration settings that have not been set.
Outdoor unit
Indoor unit
Local remote controller
Lossnay unit
M-NET Transmission cable
006
005
051
004
002
003
001
103
105
Group 2
101
Group 1
Group 3
Independent Lossnay group
Air conditioner group
1 GROUP SETTING
MENU
1
When the power is supplied to the controller, the screen shown on the left is
displayed.
2
Press the
button to select “1 GROUP SETTING”.
1
GROUP SETTING
ADDRESS
UNIT
REMOTE CONTROLLER
SYSTEM CONTROLLER
G01
The configuration setting screen is displayed.
3
Press the
button to display the group number to be set.
4
Press the
button to move the cursor to the address
display position to be set.
5
Use the numeric keypad to set the address of the indoor unit, local remote
controller, and slave system controller in the display group number.
Operation example
For an indoor unit with an address of 012.
1) Input “0”
2) Input “1”
3) Input “2”
4) Press the
button. 012
* It is also possible to enter “1” “2”.
When the input is incorrect
Press the
button and continue to input the data. After pressing the
button, move the cursor to the addresses to be deleted and press the
button to delete these addresses.
RESET
DEL.
012
01
0
GROUP
SELECT
Note:
●
Do not set Lossnay units with the intention of interlocked operation, such as Lossnay, on this group setting menu.
●
Even if the addresses are input in a non-sequential order, they will be switched to sequential order starting with the lowest
address.
●
The independent Lossnay unit cannot be set to the indoor unit group and it cannot be set as an interlocked Lossnay unit.
Summary of Contents for Lossnay PZ-41SLB-E
Page 4: ...CHAPTER 1 Ventilation for Healthy Living Lossnay Unit ...
Page 17: ......
Page 18: ...CHAPTER 2 Lossnay Construction and Principle ...
Page 24: ...CHAPTER 3 General Technical Considerations ...
Page 41: ......
Page 42: ...CHAPTER 4 Characteristics ...
Page 56: ...53 CHAPTER 4 Characteristics ...
Page 57: ...54 CHAPTER 4 Characteristics ...
Page 59: ......
Page 60: ...CHAPTER 5 System Design Recommendations ...
Page 68: ...CHAPTER 6 Examples of Lossnay Applications ...
Page 83: ......
Page 84: ...CHAPTER 7 Installation Considerations ...
Page 88: ...CHAPTER 8 Filtering for Freshness ...
Page 96: ...CHAPTER 9 Service Life and Maintenance ...
Page 98: ...CHAPTER 10 Ventilation Standards in Each Country ...
Page 101: ......
Page 102: ...CHAPTER 11 Lossnay Q and A ...
Page 108: ...Lossnay Remote Controller ...
Page 109: ......
Page 197: ...MEMO ...
Page 198: ...Y04 002 Jul 2004 MEE ...