46
Restrictions
- Airflow setting value and setting operation by unit types
3-speed model: Setting to Med.2 operates in the Med.1 airflow.
2-speed model: Setting to Med 2 or Med 1 operates in the low airflow rate.
1-speed model: Setting to Med 2, Med 1 or Low operates in the high airflow rate.
Function – [Fan Speed]
Function
[Request FanSpeed] [FanSpeed State]
Description
Setting and monitoring the airflow rate of indoor units and individually operating ventilation units (not interlocked
with indoor units).
Using NV
【
nviFanSpeed_n
】
【
nvoFanSpeed_n
】
Control unit
Indoor unit
Outline of
operation
The airflow rate (High/Med.2/Med.1/Low) for each unit is set and monitored.
②
Operation from local
remote controller
[High] operation
①
Operation from BMS
Communication Image
BMS
LM
-
AP
IC
[High] operation
state [High]
state [Low]
state [Low]
state [High]
LMAP03U