23
②
Setting for plural unit installation
When conducting initial output by installing plural LM ADAPTERs on a same system, stagger the start time of
the initial output in setting to avoid the concentration of each output.
Initialize Start Time
LMAP_001
LMAP
power source
BMS
Initialize Start Time
LMAP_002
Initialize Start Time
LMAP_003
Power ON
Standard of set time (for LMAP_002)
Initialize Start Time(LMAP_002) = Initialize Start Time(LMAP_001) + Ti
×
m
Maximum control address value of LMAP_001
:
m
(
1 to 50
)
Initialize Send Time_2 of LMAP_001
:
Ti