5.3.2 Setting relating to operation after power recovery
(1) Setting of Neuron Chip communication start time
The communication start timing of NC can be set through “Communication Timing
【
nciSet_1
】
”.
①
"initialize"
Upon completion of the connection between LM ADAPTER and air conditioner, NCstartsoperation. Up to
this time, NC will not reply (even without returning of Ack).
This operation is specifically used to acquire the state of air conditioners by Poll (Fetch)demand.
②
"setting time"
Synchronized with the shortest time among the set times of the configuration property below, NC starts
operation. Up to this time, NC will not reply (even without returning of Ack).
This operation is specially used to acquire the state of air conditioners by event (at changing) output.
- Send Start Time
【
nciStartOutTm
】
- Send Heartbeat Start Time
【
nciStartHrtBt
】
- Initialize Start Time
【
nciInitStartTm
】
Set time
[ initialize ]
[ setting time ]
LMAP power source
NC operation
(2) Setting of start time relating to event output
The start timing of event output after power recovery can be set by the configuration property shown in the
table below.
Items
Set detail and operation
Send Start Time
【
nciStartOutTm
】
The timing to start output at changing is set.
Up to the time passing the set time after power recovery, LM ADAPTER does not
output the variables even when the status of the air conditioner changes. During this
time, the air conditioner can be operated/set.
Send Heartbeat Start Time
【
nciStartHrtBt
】
The timing to start the automatic updating (periodical status notice) from LM
ADAPTER is set.
Initialize Start Time
【
nciInitStartTm
】
The timing to start the initial output is set.
To match the image of the operation information on air conditioners held by BMS and
that of the actual operation status, LM ADAPTER automatically outputs the status of
the air conditioners after power recovery.
Power ON
Related configuration property
- Send Start Time ( nciStartOutTm )
- Send Heartbeat Start Time
(
nciStartHrtBt
)
- Initialize Start Time
(
nciInitStartTm
)
Completed initialization
between LM ADAPTER
and air conditioner