34
─
Action
Checkpoint
Connect the signal cables to the
speci
fi
ed Lossnay unit.
4
10
Do the transmission cables meet regulations? (Type, diameter)
1
No.
2
Is the signal cable wired at least 5 cm away from the power supply
cable?
3
Are multiple transmission or signal cables wired to the same power
cable duct?
Are multiple signal cables wired with multi core cables?
5
Are the signal cables securely connected to the terminals?
6
Are the signal cables connected to the speci
fi
ed terminal blocks?
Mr. Slim control signal
: TM2 ,
Charged signal
: TM2 ,
Uncharged a-contact signal : TM2 ,
7
Is the wiring length of the signal cable within the regulations?
Mr. Slim control signal
: Total extension within 500 m
Charged signal
: Within limitation of the external device
Uncharged a-contact signal : Total extension within 500 m
Use speci
fi
ed cables.
Wire the signal cable at least 5
cm away from the power supply
cable.
Wire the transmission cables
away from the signal cables.
Using suitable cables, wire the
signal cables so that they are
separated from one another.
Connect them securely.
Connect them to the speci
fi
ed
terminal blocks.
Wire the cables within the regula-
tions.
Signal cables from external devices (Table 1-1-3)
Check the following checkpoints when connecting with level signal/pulse signal output devices, and Mr. Slim units.
8
Input a signal that suits the speci-
fi
cations.
Do the external signals meet speci
fi
cations?
Level signal: Charged 12 V DC/ 24 V DC, uncharged a-contact
Pulse signal: Charged 12 V DC/ 24 V DC, uncharged a-contact
(A pulse width of 200 ms or greater is required)
9
<When using PZ-60DR-E>
Check the pulse input setting from
the function selection. (Refer to
page 29)
<When not using PZ-60DR-E>
Check the setting of the pulse
input switch (SW2-2) on the
Lossnay circuit board. (Refer to
page 25)
Are the type of input signal and the setting of the pulse input matched?
Pulse signal
: ON setting
Other than pulse signal : OFF setting
In a system with multiple Lossnay units, are the signal cables con-
nected to the speci
fi
ed Lossnay unit?
Basic system (PZ-60DR-E, PZ-41SLB-E):
Lossnay unit for which the Main/Sub selection switch (SW1) is set to
“Main”
M-Net control:
Lossnay unit that is set to the address with the smallest number
within the group
11
When PZ-60DR-E is not used, are the function selection switches
(SW2, SW5) on the Lossnay circuit board set correctly?
Set the switches correctly to cor-
respond with the application.
(Refer to page 25 and 26)
12
When PZ-60DR-E is used, is the function selection set correctly?
Set it correctly to correspond with
the application.
(Refer to page 27 to 29)