13
─
Extra High
/High
Fan speed
selection
Multi ven-
tilation
mode
Power
supply/
exhaust
mode
( When
operation
starts )
The fan speed can be selected either High or Extra High, when
the speed is set High with the remote controller or the system
controller. Select Extra High when large air volume is required,
or when the ductwork length is long.
When set to High fan speed, High/Low fan speed can be
switched, and when set to Extra High fan speed, Extra High/
Low fan speed can be switched.
Air supply SW2-9
: ON
Exhaust SW2-10
: ON
( Refer to page
25)
SW2-3: ON
( Refer to page
25)
When PZ-60DR-E will not be used in a system of
multiple Lossnay units, set the function selection
switches on the Lossnay circuit board for each
unit.
The fan speed display of the remote controller,
and the system controller will be the same for
either Extra High or High.
Fan speed control by function setting
The following fan speed control can be set with PZ-60DR-E or the function selection switch (SW2) on the
Lossnay circuit board.
Function
PZ-60DR-E
(Remote controller
function selection)
PZ-60DR-E Not Used
(Function selec-
tion switch)
Supply fan
speed setting
Extra High SH: L
High
H: L
Exhaust fan
speed setting
Extra High SH: L
High
H: L
( Refer to page
28)
Supply fan
speed setting
Multiple ventila-
tion
: L
Exhaust fan
speed setting
Multiple ventila-
tion
: L
( Refer to page
28)
Air supply SW2-4
: ON
Exhaust SW2-5
: ON
( Refer to page
25)
The settable fan speed with the remote controller or the sys-
tem controller can be fixed at Low. The supply/exhaust balance
is adjusted to suit the usage environment or the place of instal-
lation.
Power supply/
exhaust when
operation starts :
ON
( Refer to page
28)
During the first 30 minutes of operation, operation will be at
High (Extra High) fan speed. This is used when rapid ventila-
tion is desired at the time of starting operation.
After 30 minutes have elapsed since starting operation, or
when the fan speed set from the remote controller or the sys-
tem controller has been changed to something other than High
fan speed, power ventilation will be cancelled and the system
will follow the fan speed set by the remote controller or system
controller.
Details
Setting Method
Display
Multiple
units
When PZ-60DR-E will not be used in a system of
multiple Lossnay units, set the function selection
switches on the Lossnay circuit board for each
unit.
When both supply and exhaust are set to the multi
ventilation mode, due to operation restrictions
PZ-60DR-E cannot be switched to a setting other
than Low fan speed. Other remote controllers and
system controllers can change the fan speed dis-
play; however, the fan will remain fixed at Low fan
speed.
Operation
Multiple
units
When PZ-60DR-E will not be used in a system of
multiple Lossnay units, set the function selection
switches on the Lossnay circuit board for each
unit.
During power ventilation, PZ-60DR-E will display
“POWER VENT START”. Other remote control-
lers and system controllers will display the set fan
speed, even during power supply exhaust opera-
tion.
Display
Multiple
units