![Mitsubishi Electric FX3U-1PG User Manual Download Page 130](http://html.mh-extra.com/html/mitsubishi-electric/fx3u-1pg/fx3u-1pg_user-manual_238960130.webp)
Appendix B: Example Connection
Appendix B-1 Example of Connection with MR-J4-[ ]A Servo Amplifier
124
FX
3U
-1PG User's Manual
Appendix B: Example Connection
This chapter explains FX
3U
-1PG connected to a FX
3U
Series PLC (AC power supply type), and examples of
connection with the servo amplifier and stepping motor driver.
For details of other PLC, servo amplifier and stepping motor driver, refer to the manual of each product.
Appendix B-1 Example of Connection with MR-J4-[ ]A Servo Amplifier
*1.
Set the command pulse input form of the servo amplifier (PA13) MR-J4- A to “021*” (negative logic,
command input pulse train filter: 500 kpps or less).
In “*”, set “0” when the pulse output type of FX
3U
-1PG is “Forward/reverse pulse train”, and set “1”
when it is “Pulse train + Direction”.
P
C
CN2
L1
L2
U
V
W
L
24V
X000
X001
X002
X003
X004
X005
X006
X007
RA1
RA2
24 V DC
power supply
RA3
X010
S/S
DOG
STOP
COM1
CLR
PG0+
PG0-
FP
COM0
RP
STOP
Error reset
Forward limit
Reverse limit
Forward JOG
Reverse JOG
Zero return
command
Start
Servo ready
Positioning
completion
Servo failure
X011
X012
0V
S/S
MR-J4-
A
Servo amplifier
*1
To servo
motor
Main circuit
power supply
FX
3U
-1PG
FX
3U
Series
PLC
Regenerative
option
LSD
STOP
Cable length:
2 m or less
Cable length:
2 m or less
Cable length:
2 m or less
Encoder
RD 49
N
VIN
RA1
CR 41
P15R 1
OP 33
CN1
CN1
RA2
RA3
DOCOM
NP 35
DICOM
OPC
SD
12
PP
Plate
20
46
10
AC power supply
Class-D
grounding
LSN
EM2
44
42
DOCOM 47
SON
RES
15
LSP 43
19
INP
ALM
24
48
DICOM 21
L3
CN1
Summary of Contents for FX3U-1PG