13
ENGLISH
8.3. Electrical wiring diagram
■
GUF-50
•
100RDH3
•
TM1, TM2, TM3 shown in dotted lines are field work.
•
Be sure to connect the grounding wire.
•
Breakers and controller switches should be provided by the customer.
■
SYMBOL EXPLANATION
■
NOTE 1. TM1,TM2,TM3 shown in dotted lines are field work.
2. Be sure to connect the grounding wire.
3. Breakers should be provided by the customer.
4. MARK
: indicates terminal block, : connector,
: board insertion connector or fastening connector of control board.
GUF50-100RDH3
M1
M2
C
W.S
SV1
SV2
TH1
TH2
TH3
TH4
LEV
RSV
Symbol
Name
Symbol
Name
Symbol
Name
TM1
TM2
TM3
SW1
SW2
SW3
SW4
SW5
SW11
SW12
SW14
1, 2
A, B
S
CND1, CND2
X02–X09
TR
GM
LS
LED1
LED2
LED3
Fan motor (exhaust)
Fan motor (supply)
Capacitor
Water sensor
Solenoid valve (pressure regulator)
Solenoid valve (exhaust)
Thermistor (outdoor air temp. detection)
Thermistor (pipe temp. detection/liquid)
Thermistor (pipe temp. detection/gas)
Thermistor (room air temp. detection)
Electronic linear expansion valve
Resistance(solenoid valve)
Terminal block (power supply)
Terminal block (transmission)
Terminal block (humidistat, monitor)
Switch (function selection)
Switch (capacity code setting)
Switch (function selection)
Switch
Switch
Switch (1st digit address set)
Switch (2nd digit address set)
Switch (branch NO. set)
Remote control terminal
M-NET transmission terminal
Shield
Connector (power supply)
Relay
Transformer
Damper motor
Limit switch
Power supply monitor
MA Remote contoller Power supply monitor
M-NET Power supply monitor
1
12
11
10
9
8
7
2
A
B
S
GREEN/YELLOW
BLACK
PINK
ORANGE
WHITE
RED
GREEN/YELLOW
SUPPLY FAN
EXHAUST FAN
ORANGE
BLUE
WHITE
RED
BLACK
PINK
GREEN/YELLOW
M2
M1
BROWN
PINK
PINK
C
C
7
1
5
5
1
ZNR901
ZNR902
DSA1
X05
X04
X07
X06
FUSE1
PURPLE
FAN1
FAN4
CND1
CND2
BLACK
YELLOW
YELLOW
RED
WHITE
WHITE
ORANGE
PURPLE
FAN2
FAN3
SW4
SW5
SV2
SV1
DB901
1
6
1
X02
RSV (1K
Ω
)
RED
YELLOW
YELLOW
YELLOW
ORANGE
ORANGE
LS
W.S
GM
RED
RED
PURPLE
PURPLE
CN70
CNL
CN27
CN4D
RED
RED
Liquid
pipe
Gas
pipe
TH4 (RA)
TH1 (OA)
YELLOW
YELLOW
WHITE
WHITE
PINK
PINK
GRAY
GRAY
CN22
CN29
CN21
CN20
TH2
TH3
250V 6.3A
SW1
SW2
SW3
SW12
LED1
LED2
SW11
SW14
LED3
BROWN
RED
PURPLE
ORANGE
PINK
WHITE
LEV
CN60
3
1
TM1
BROWN
BROWN
BLUE
RED
BLUE
BROWN
/YELLOW
TR
CN3T
CNT
GREEN
N
L
TM3
TM2
PE
N
L
BREAKER(16A)
220-240V ~ 50Hz
POWER SUPPLY
X09
X08
X03
<PAR-F27MEA>
<PAR-20MAA>
Remote Controller
Uncharged a-contact
Humidistat
240VAC more than 10mA
Operation monitor output
AC240V 1A
AC220V 100mA
DC 24V 1A
DC 5V 100mA
MAX MIN
Malfunction monitor output
MAX MIN
AC240V 1A
AC220V 100mA
DC 24V 1A
DC 5V 100mA
Shield wire
M-NET Remote controller
Fresh Master
To Outdoor Unit , BC Controller
M-NET transmissiion cable
■
Warning
Before obtaining access to terminals, all supply circuits
must be disconnected.