Common specifications
*1
Can be displayed only on the operation panel (FR-DU07).
*2
Can be displayed only on the parameter unit (FR-PU04).
*3
Temperature applicable for a short period in transit, etc.
*4
Only the 01800 or more functions.
*5
2.9m/s
2
or less for the 04320 or more.
D
is
pl
ay
PU
(FR-DU07/
FR-PU04)
Operating
status
Output frequency, motor current (steady or peak value), output voltage, alarm indication,
frequency setting, running speed, converter output voltage (steady or peak value), electronic
thermal relay function load factor, input power, output power, load meter, cumulative energization
time, actual operation time, motor load factor, cumulative power, power saving effect, cumulative
saving power, regenerative brake duty
,PID set point, PID measured value, PID deviation value,
inverter I/O terminal monitor, input terminal option monitor
, output terminal option monitor
option fitting status monitor
Alarm
definition
Alarm definition is displayed during the protective function is activated, output voltage/
current/frequency/cumulative energization time and eight past alarm definition is stored.
Interactive
guidance
Operation guide/trouble shooting with a help function
Protective/warning function
Overcurrent during acceleration, overcurrent during constant speed, overcurrent during
deceleration, overvoltage during acceleration, overvoltage during constant speed, overvoltage
during deceleration, inverter protection thermal operation, motor protection thermal operation,
heatsink overheat, instantaneous power failure occurrence, undervoltage, input phase failure,
motor overload, output side earth fault overcurrent, output phase failure, external thermal relay
operation, PTC thermistor operation, option alarm, parameter error, PU disconnection, retry
count excess, CPU alarm, operation panel power supply short circuit, 24VDC power output
short circuit, output current detection value excess, inrush current limit circuit alarm,
communication alarm (inverter), analog input alarm, internal circuit error (15V power supply),
fan fault, overcurrent stall prevention, overvoltage stall prevention, electronic thermal relay
function prealarm, PU stop, maintenance timer alarm
, brake transistor alarm detection
parameter write error, copy operation error, operation panel lock, parameter copy
E
n
vi
ronm
e
n
t
Ambient
temperature
LD
-10°C to +50°C (non-freezing)
SLD
(initial setting)
-10°C to +40°C (non-freezing)
Ambient humidity
90%RH or less (non-condensing)
Storage temperature
-20°C to +65°C
Atmosphere
Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt etc.)
Altitude, vibration
Maximum 1000m above sea level for standard operation. After that derate by 3% for every
extra 500m up to 2500m (92%) 5.9m/s
2
or less