16
2.2 Wiring
2.2.1
Terminal connection diagram
!
!
!
!
3-phase 200V power input
!
!
!
!
3-phase 400V power input
Note: 1. If the potentiometer is to be operated often, use a 2W1k
Ω
potentiometer.
2. 0.1K and 0.2K do not contain a transistor.
3. Terminals SD and SE are isolated.
4. Term inals S D and 5 are co m m on term inals. D o not earth (ground) them to the
ground . Term inals S D and 5 are not isolated. (T hose of the 400V class are isolated.)
5. When terminals PC-SD are used as a 24VDC power supply, be careful not
to short these terminals. If they are shorted, the inverter will be damaged.
6. N ot needed w hen the operation panel or param eter unit (F R -PU 04) is used for
calibration. U sed w hen calibration m ust be m ade near the frequency m eter for
such a reason as a rem ote frequency m eter. H ow ever, the frequency m eter
needle m ay not deflect to full-scale if the calibration resistor is connected. In this
case, use this resistor and the operation panel or param eter unit together.
3-phase AC
power supply
NFB
STF
STR
RH
RM
RL
MRS
RES
Forward rotation start
Middle
High
Low
Output stop
Reset
Frequency setting signals (Analog)
10(+5V)
2
2
3
1
4 to )
4(4 to 20mADC)
1/2W1k
Ω
RUN
FU
SE
Running
Frequency detection
Jumper
Remove this jumper when
using the optional power-factor
improving DC reactor.
Brake resistor connection
Motor
IM
Alarm
output
A
B
C
U
V
W
P1
PR
0 to 5VDC
0 to 10VDC
Selected
Multi-speed selection
Open
collector outputs
5
(Note 1)
Frequency
setting
potentiometer
Current input(-)
Reverse rotation start
MC
Open collector
output common
Main circuit terminal
Control circuit input terminal
Control circuit output terminal
When using current input as the
frequency setting signal, set "4" in
any of Pr.180 to Pr.183 (input
terminal function selection) and
assign AU (current input selection)
to any of terminal RH, RM, RL, or
MRS, then turn the AU signal on.
Operation panel
(With frequency setting
potentiometer)
PU connector
(RS-485)
PC
24VDC power output and
external transistor common
Note 5
Contact input common
Control input signals
(No voltage input allowed)
SD
Note 4
FM
SD
Meter
(e.g. frequency meter)
+
Moving-coil type
1mA full-scale
-
Note 3
Calibration
resistor (Note 6)
R(L
1
)
S(L
2
)
T(L
3
)
(+)P
(-)N
Note 4
Note 2
Earth
(ground)
Note 3
Earth
(ground)
(Common)