INSTALLATION OF THE INVERTER AND INSTRUCTIONS
2.4
Installation of the Inverter
Enclosure surface mounting
Remove the front cover and wiring cover to fix the inverter to the surface.
Front cover
Wiring cover
Front cover
FR-D720S-008SC to 042SC
FR-D720S-070SC and 100SC, FR-D740-012SC to 160SC
Wiring cover
NOTES
앫
When encasing multiple inverters,
install them in parallel and leave
clearance as a cooling measure.
앫
Install the inverter vertically.
ve
rt
ical
Refer to the cle
arances besid
e
Ambient temperature and humidity
Clearances (front)
Clearances (side)
5 cm
5 cm
5 cm
Inve
rt
er
Measurement
position
Measurement
position
Temperature: –10 °C to +50 °C
Humidity:
90 % RH maximum
10 cm or more
1 cm
or more
*1
10 cm or more
1 cm
or more
*1
1 cm
or
more
*1
Leave enough clearances and
take cooling measures.
*1
When using the inverters at the
ambient temperature of 40 °C or less,
the inverters can be installed
closely attached (0 cm clearance).
When ambient temperature exceeds
40 °C, clearances between the inverter
should be 1 cm or more (5 cm or more
for the FR-D740-120SC or more).
*1
5 cm or more for the
FR-D740-120SC or more