10
WIRING
4.4.3 Wiring Method
Use a bar terminal and a cable with a sheath stripped off for the control circuit wiring. For a single wire, strip off the sheath of the
cable and apply directly. Insert the bar terminal or the single wire into a socket of the terminal.
앫
Strip off the sheath about the length below. Wire the stripped cable after twisting it to prevent it from becoming loose.
In addition, do not solder it.
앫
Crimp the bar terminal.
Insert wires to a bar terminal, and check that the wires come out for about 0 to 0.5 mm from a sleeve.
앫
Check the condition of the bar terminal after crimping. Do not use a bar terminal of which the crimping is inappropriate, or the
face is damaged.
앫
Introduced products on bar terminals:
*1
A bar terminal with an insulation sleeve compatible with MTW wire which has a thick wire insulation
*2
Applicable for terminal ABC
Wire Size [mm²]
Bar Terminal Model
Bar Terminal
Crimping Tool
With Insulation Sleeve
Without Insulation Sleeve
For UL Wire
*1
0.3
AI 0,5-10WH
—
—
CRIMPFOX 6
(Phoenix Contact
Co., Ltd.)
0.5
AI 0,5-10WH-GB
0.75
AI 0,75-10GY
A 0,75-10
AI 0,75-10GY-GB
1
AI 1-10RD
A 1-10
AI 1-10RD/1000GB
1.25/1.5
AI 1,5-10BK
A 1,5-10
AI 1,5-10BK/1000GB
*2
0.75 (for two cables)
AI-TWIN 2
×
0,75-10GY
—
—
Wire Size [mm²]
Bar Terminal
Product Number
Insulation
Product Number
Bar Terminal Crimping Tool
0.3 to 0.75
BT 0.75-11
VC 0.75
NH 67 (NICHIFU Co., Ltd.)
10 mm
Shell
0–
0,5
m
m
Cable
Sleeve
Wires are not inserted
into the shell
Crumpled tip
Unstranded
wires
Damaged
Summary of Contents for FR-D720S-008SC