Peripheral devices
16
control
When a multi-wound motor is connected under Real sensorless vector control or Vector control
Select an MCCB according to the power supply capacity.
Install one MCCB per converter circuit in the converter unit.
For the use in the United States or Canada, provide appropriate fuses in accordance with any applicable local codes.
The magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the
magnetic contactor is used for emergency stops during motor driving, the electrical durability is 25 times.
When using an MC for emergency stop during driving the motor, select the MC with JEM 1038-AC-3 class rated current for the converter unit
input current. When providing an MC on the inverter output side for switching to commercial power supply during general-purpose motor
operation, select the MC with JEM 1038-AC-3 class rated current for the rated motor current.
• Option 3
To connect the equipment to the output side of the 12-phase rectifier transformer after branching, refer to the following table
and prepare appropriate equipment.
When a single wound motor or a multi-wound motor is connected under V/F control or Advanced magnetic flux vector
control
When a multi-wound motor is connected under Real sensorless vector control or Vector control
Select an MCCB according to the power supply capacity.
Install one MCCB per converter circuit in the converter unit.
For the use in the United States or Canada, provide appropriate fuses in accordance with any applicable local codes.
The magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the
magnetic contactor is used for emergency stops during motor driving, the electrical durability is 25 times.
When using an MC for emergency stop during driving the motor, select the MC with JEM 1038-AC-3 class rated current for the converter unit
input current. When providing an MC on the inverter output side for switching to commercial power supply during general-purpose motor
operation, select the MC with JEM 1038-AC-3 class rated current for the rated motor current.
Number of
units in
parallel
Applicable
converter unit
FR-CC2-[ ]-P
Rated input current
for one circuit
(A)
Molded case circuit breaker
(MCCB)
(NF type)
(A)
Magnetic contactor
(MC)
on converter
unit's input side
2
H400K
819
1000
900 A rated product
H450K
922
1200
1000 A rated product
H500K
1024
1300
1100 A rated product
H560K
1165
1500
1300 A rated product
3
H400K
1229
1500
1400 A rated product
H450K
1382
1700
1500A rated product
H500K
1536
2000
1700A rated product
H560K
1747
2200
1900A rated product
Number of
units in
parallel
Applicable
converter unit
FR-CC2-[ ]-P
Rated input current
for one circuit
(A)
Molded case circuit breaker
(MCCB)
(NF type)
(A)
Magnetic contactor
(MC)
on converter
unit's input side
2
H400K
1024
1300
1100 A rated product
H450K
1152
1500
1300 A rated product
H500K
1280
1600
1400 A rated product
H560K
1456
1800
1600 A rated product
Applicable
converter unit
FR-CC2-[ ]-P
Rated input current
for one circuit
(A)
Molded case circuit breaker
(MCCB)
(A)
Magnetic contactor
on converter
unit's input side
H315K
406
500
S-N400
H355K
454
600
S-N400
H400K
512
600
S-N600
H450K
576
700
S-N600
H500K
640
800
S-N600
H560K
728
900
S-N800
H630K
806
1000
S-N800
Applicable
converter unit
FR-CC2-[ ]-P
Rated input current
for one circuit
(A)
Molded case circuit breaker
(MCCB)
(A)
Magnetic contactor
on converter
unit's input side
H400K
512
600
S-N600
H450K
576
700
S-N600
H500K
640
800
S-N600
H560K
728
900
S-N800