(N) Operation via communication and its settings
115
5
GROUP
N
5.7
(N) Operation via communication and its
settings
5.7.1
Wiring and configuration of PU connector
Using the PU connector enables communication operation from a personal computer, etc.
When the PU connector is connected with a personal, FA or other computer by a communication cable, a user program can
run to monitor the converter unit or read and write parameters.
PU connector pin-outs
NOTE
• Pins No. 2 and 8 provide power to the operation panel. Do not use these pins during RS-485 communication.
• Do not connect the cable to a computer's LAN board, to a fax modem socket, or to a telephone connector. Doing so may
damage the product due to the differences in the electric specifications.
Purpose
Parameter to set
Refer to
page
To start operation via
communication
Initial setting of operation via
communication
P.N001
Pr.342
To operate via
communication from PU
connector
Initial setting of computer link
communication (PU connector)
P.N020 to P.N028
Pr.117 to Pr.124
To set the signal loss
detection time for parallel
operation communication.
Parallel operation communication
check time
P.N092
Pr.652
Pin
number
Name
Description
1
SG
Earthing (grounding)
2
-
Operation panel power supply
3
RDA
Converter unit
4
SDB
Converter unit send-
5
SDA
Converter unit send+
6
RDB
Converter unit receive-
7
SG
Earthing (grounding)
8
-
Operation panel power supply
8
1
Converter unit
(Receptacle side)
Front view
to