(M) Monitor display and monitor output signal
102
Monitor item list (Pr.774 to Pr.776, Pr.992)
• The monitor items of the FR-CC2-P (including the availability for the master and the slave during the parallel operation) is
as follows.
indicates that the monitor is valid.
indicates that the monitor is invalid ("0" is displayed). Use
Pr.774 to
Pr.776 and Pr.992
to select a monitored item to be displayed on the operation panel.
• Refer to the following table and set the monitor to be displayed. (The items with — are not available for monitoring.) The
circle in the minus (—) display column denotes availability of the minus sign display.
The cumulative energization time is accumulated from 0 to 65535 hours, then cleared, and accumulated again from 0.
Since the voltage and current display on the operation panel is shown in four digits, a monitor value of more than "9999" is displayed as "----".
0 A appears during regenerative driving.
Input terminal monitor details ("1" denotes terminal ON, "0" denotes terminal OFF, and "
─
" denotes undetermined value.)
Output terminal monitor details ("1" denotes terminal ON, "0" denotes terminal OFF, and "
─
" denotes undetermined value.)
The monitored values are retained even if a converter unit fault occurs. Resetting will clear the retained values.
The total input current of the master and slave converter units is displayed. If the current is 5% or less of the rated input current of the converter
unit multiplied by the number of units operated in parallel, "0" is displayed.
Pr.774 to
Pr.776,
Pr.992
RS-485
communication
dedicated
monitor
(hexadecimal)
Types of monitor
Unit
Minus (
-)
di
sp
la
y
Description
Ma
ster station
Slave
sta
tio
n
2
H02
Input current
0.1 A
Displays the converter unit input current
effective value.
8
H08
Converter output
voltage
0.1 V
Displays the DC bus voltage value.
13
H0D
Input power
0.1 kW
Displays the power at the converter unit input
side.
20
H14
Cumulative
energization time
1 h
Displays the cumulative energization time
since the converter unit shipment. Check how
many times the monitor value exceeded 65535
h with
Pr.563
.
25
H19
Cumulative power
0.1 kWh
Displays the cumulative energy based on the
input power monitor.
This can be cleared by
Pr.170
.
(Refer to
43
H2B
Parameter for manufacturer check. Do not set.
44
H2C
Station number (PU)
1
Displays which station number (0 to 31) can
currently be used for communication from the
PU connector.
55
H0F
Input terminal status
—
Displays input terminal ON/OFF state of the
converter unit. (For operation panel indication,
refer to
H10
Output terminal status —
Displays output terminal ON/OFF state of the
converter unit. (For operation panel indication,
refer to
62
H3E
Electric thermal relay
function load factor
0.1%
Displays the accumulated heat value of the
converter thermal O/L relay.
The converter overload trip (electronic thermal
relay function) (E.THC) occurs at 100%.
68
H44
Emergency drive
status
1
Displays the emergency drive status
—
H4D
32-bit cumulative
power (lower 16 bits)
1 kWh
Displays the 32-bit cumulative power value in
multiplies of 16 bits.
Monitoring can be performed via RS-485
communication.
—
H4E
32-bit cumulative
power (upper 16 bits)
1 kWh
—
H4F
32-bit cumulative
power (lower 16 bits)
0.1 kWh
—
H50
32-bit cumulative
power (upper 16 bits)
0.1 kWh
98
H62
Control circuit
temperature
1°C
Displays the temperature of the control circuit
board.
Without minus sign: 0 to 100°C
With minus sign: -20 to 100°C
b15
b0
─
─
─
─
─
RES
─
OH
─
─
─
─
─
─
─
RDI
b15
b0
─
─
─
─
─
─
─
─
─
─
ABC1
FAN
RSO
IPF
RDA
RDB