PPO TYPE NON-SUPPORT SPECIFICATION
Inverter status/operation command
The inverter status can be monitored and operation command can be given from the master.
Signal names are initial values. Using
Pr.180 to Pr.187
, you can change output signal functions. Refer to the Instruction Manual
(Detailed) of the inverter for details of
Pr.180 to Pr.187
.
For the FR-F800 series, no function is assigned in the initial setting.
IND
PNU
Item
H0100
HA
Inverter status
For details, refer to ZSW on
Run command
Bit
Name
Definition
0
—
Not used (0 is set)
1
Terminal STF
Forward rotation command
Functions assigned to the terminals
RH, RM, RL, JOG, RT, AU, CS and
MRS are activated.
2
Terminal STR
Reverse rotation command
3
Terminal RH
High-speed operation command
4
Terminal RM
Middle-speed operation command
5
Terminal RL
Low-speed operation command
6
Terminal JOG
JOG operation selection
7
Terminal RT
Second function selection
8
Terminal AU
Terminal 4 input selection
9
Terminal CS
Restart after instantaneopus power failure
selection
10
Terminal MRS
Inverter output shut off
11 to 15
—
Not used (0 is set)