PPO TYPE SUPPORT SPECIFICATION
53
7
Valid only for the FR-A800 series when
Pr.1110 PROFIBUS format selection
= "1" (extended format). (Refer to
PZD enable and command count request can be executed.
If it takes time to perform slave side processing, slave side busy status is announced since reply to the master will be delayed. During
busy status, other response data are unfixed values. When the slave side is busy, request from the master is invalid. Therefore, the same
request must be sent again. The response data of the FR-A8NP during Busy status is as follows.
When a value other than 9999 is set in
Pr.430 Pulse monitor selection
under position control (
Pr.800
="3, 4") for the FR-A800 series,
pulse monitor is selected. (Refer to the Instruction Manual (Detailed) of the inverter for pulse monitor.)
Signal names are initial values. Using
Pr.180 to Pr.186
, you can change output signal functions. Refer to the Instruction Manual
(Detailed) of the inverter for details of
Pr.180 to Pr.186
.
For the FR-F800 series, no function is assigned in the initial setting.
These signals are set in the initial setting. Using
Pr.190
, output signal assigned to the device number can be changed.
For the details of
Pr.190
, refer to the Instruction Manual (Detailed) of the inverter.
NOTE
• Only when the contents of the command request (request for changing the inverter setting: PKW, HSW, STW/ECW)
from the master changed, the inverter processes the request. If the contents of the command request are identical
with those of the last request, the inverter does not process the request. (The received request is cleared.)
For instance, while the master keeps sending the "network operation mode enable" command, changing the mode to
the PU operation mode with switchover function does not allow the "network operation mode enable" command to be
executed due to the same contents as that sent last time. Therefore, the operation mode remains the PU operation
mode without changing to the Network operation mode. In this case, send another command as "PU operation mode
enable" from the master once, then send the "network operation mode enable" command again.
ID
During busy status and
inverter reset
During busy status and
other than inverter rest
PKW
0
All 0 when AK="0"
Reply data when AB
"0"
PZD
ZSW Bit 15 (BUSY) ="1"
Other error Bit="0"
ZSW Bit 15 (BUSY) ="1"
Other error Bit=inverter status data
Summary of Contents for FR-A8NP
Page 7: ...6 MEMO ...