Communication connectors and terminals
58
USB device communication
A USB (Ver. 1.1) cable connects the inverter with a personal computer.
Parameter setting and monitoring can be performed by FR Configurator 2.
NOTE
• For the details of FR Configurator2, refer to the Instruction Manual of FR Configurator2.
2.7.3
RS-485 terminal block (RS-485 model)
Communication operation
The RS-485 terminals enables communication operation from a personal computer, etc. When the PU connector is connected
with a personal, FA or other computer by a communication cable, a user program can run to monitor the inverter or read and
write parameters.
Communication can be performed with the Mitsubishi inverter protocol (computer link operation) and MODBUS RTU protocol.
(For details, refer to the FR-A800 Instruction Manual (Detailed).)
NOTE
• To avoid malfunction, keep the RS-485 terminal wires away from the control circuit board.
• For wiring of the RS-485 terminals used with a plug-in option, lead the wires on the left side of the plug-in option.
Interface
Conforms to USB 1.1
Transmission speed
12 Mbps
Wiring length
Maximum 5 m
Connector
USB mini B connector (receptacle)
Power supply
Self-powered
Conforming standard
EIA-485 (RS-485)
Transmission format
Multidrop link
Communication speed
115200 bps maximum
Overall length
500 m
Connection cable
Twisted pair cable (4 pairs)
Terminating resistor switch
Initially-set to "OPEN".
Set only the terminating resistor switch of
the remotest inverter to the "100Ω" position.
OPEN
100Ω
+
-
+ TXD
RXD
-
VCC GND
+
-
+ TXD
RXD
-
VCC GND
RDA1
(RXD1+)
RDB1
(RXD1-)
RDA2
(RXD2+)
RDB2
(RXD2-)
SDA1
(TXD1+)
SDB1
(TXD1-)
SDA2
(TXD2+)
SDB2
(TXD2-)
P5S
(VCC)
SG
(GND)
P5S
(VCC)
SG
(GND)