Main circuit terminals
36
2.5
Main circuit terminals
2.5.1
Details on the main circuit terminals of the
inverter
2.5.2
Details on the main circuit terminals of the
converter unit (FR-CC2)
Terminal
symbol
Terminal name
Terminal function description
Refer
to page
U, V, W
Inverter output
Connect these terminals to a three-phase squirrel cage motor.
-
R1/L11,
S1/L21
Power supply for the control
circuit
Connected to terminals P/+ and N/-. To retain the fault display and fault
output, or to use the converter unit (FR-CC2), remove the jumpers installed in
terminals R1/L11 and S1/L21, and apply external power supply to these
terminals.
The power capacity necessary when separate power is supplied from R1/L11
and S1/L21 is 80 VA.
P/+, N/-
Converter unit connection
Connect the converter unit (FR-CC2), brake unit (FR-BU2), or high power
factor converter (FR-HC2).
,
Earth (ground)
For earthing (grounding) the inverter chassis. This must be earthed
(grounded).
Terminal
symbol
Terminal name
Terminal function description
Refer
to page
R/L1,
S/L2,
T/L3
AC power input
Connect these terminals to the commercial power supply. (When the
converter unit is connected to the 12-phase rectifier power transformer, refer
to the Instruction Manual of the FR-CC2.)
-
R1/L11,
S1/L21
Power supply for the control
circuit
Connected to the AC power supply terminals R/L1 and S/L2. To retain the
fault display and fault output, remove the jumpers across terminals R/L1 and
R1/L11 and across S/L2 and S1/L21, and supply external power to these
terminals.
The power capacity necessary when separate power is supplied from R1/L11
and S1/L21 is 80 VA.
P/+, N/-
Inverter connection
Connect to terminals P/+ and N/- of the inverter.
Earth (ground)
For earthing (grounding) the converter unit chassis. This must be earthed
(grounded).