Inverter rating
110
6.1
Inverter rating
400 V class
• Inverter
∗1
The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi Electric 4-pole standard motor.
∗2
For the SND rating, the carrier frequency is always 2 kHz.
∗3
The rated output capacity indicated assumes that the output voltage is 440 V.
∗4
The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty,
allow time for the inverter and motor to return to or below the temperatures under 100% load.
∗5
The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range.
However, the maximum point of the voltage waveform at the inverter output side is the power supply voltage multiplied by about
.
∗6
ND rating reference value
∗7
FR-DU08: IP40 (except for the PU connector section)
∗8
For the power voltage exceeding 480 V, set
Pr.977 Input voltage mode selection
. (For details, refer to the FR-A800 Instruction Manual
(Detailed).)
Model FR-A842-[ ]-R2R
315K
355K
400K
450K
500K
07700
08660
09620
10940
12120
Applicable motor
capacity (kW)
SLD
400
450
500
560
630
LD
355
400
450
500
560
SND
355
400
450
500
560
ND (initial setting) 315
355
400
450
500
HD
280
315
355
400
450
Output
Rated capacity
(kVA)
SLD
587
660
733
834
924
LD
521
587
660
733
834
SND
521
587
660
733
834
ND (initial setting) 465
521
587
660
733
HD
417
465
521
587
660
Rated current (A)
SLD
770
866
962
1094
1212
LD
683
770
866
962
1094
SND
683
770
866
962
1094
ND (initial setting) 610
683
770
866
962
HD
547
610
683
770
866
Overload current
rating
SLD
110% 60 s, 120% 3 s (inverse-time characteristics) at surrounding air temperature of 40°C
LD
120% 60 s, 150% 3 s (inverse-time characteristics) at surrounding air temperature of 50°C
SND
150% 60 s (inverse-time characteristics) at surrounding air temperature of 50°C
ND (initial setting) 150% 60 s, 200% 3 s (inverse-time characteristics) at surrounding air temperature of 50°C
HD
200% 60 s, 250% 3 s (inverse-time characteristics) at surrounding air temperature of 50°C
Rated voltage
Three-phase 380 to 500 V
Regenerative
braking torque
(When the
converter unit
(FR-CC2) is used)
Maximum brake
torque
10% torque/continuous
Input powe
r DC power supply voltage
430 to 780 VDC
Control power supply auxiliary input
Single phase 380 to 500 V 50 Hz/60 Hz
Permissible control power supply
auxiliary input fluctuation
Frequency
±
5%, voltage
±
10%
Protective structure (IEC 60529)
Open type (IP00)
Cooling system
Forced air cooling
Approx. mass (kg)
163
163
243
243
243