13
PARAMETER
50
Second output
frequency detection
0 to 400Hz
30Hz
51
Second electronic
thermal O/L relay
0 to 500A, 9999
9999
52
DU/PU main display
data selection
0, 5 to 8, 10 to
14, 17 to 20, 22
to 25, 32 to 35,
50 to 57, 100
0
54
FM terminal function
selection
1 to 3, 5 to 8, 10
to 14, 17, 18, 21,
24, 32 to 34, 50,
52, 53
1
55
Frequency monitoring
reference
0 to 400Hz
60Hz
56
Current monitoring
reference
0 to 500A
Rated
inverter
output
current
57
Restart coasting time
0, 0.1 to 5s,
9999
9999
58
Restart cushion time
0 to 60s
1s
59
Remote function
selection
0, 1, 2, 3
0
60
Energy saving control
selection
0, 4
0
61
Reference current
0 to 500A, 9999
9999
62
Reference value at
acceleration
0 to 220%, 9999
9999
63
Reference value at
deceleration
0 to 220%, 9999
9999
64
Starting frequency for
elevator mode
0 to 10Hz, 9999
9999
65
Retry selection
0 to 5
0
66
Stall prevention
operation reduction
starting frequency
0 to 400Hz
60Hz
67
Number of retries at
fault occurrence
0, 1 to 10,
101 to 110
0
68
Retry waiting time
0 to 10s
1s
69
Retry count display
erase
0
0
71
Applied motor
0 to 8, 13 to 18,
30, 33, 34, 40,
43, 44, 50, 53,
54
0
72
PWM frequency
selection
0 to 15
2
73
Analog input selection
0 to 7, 10 to 17
1
74
Input filter time
constant
0 to 8
1
75
Reset selection/
disconnected PU
detection/PU stop
selection
0 to 3, 14 to 17
14
76
Alarm code output
selection
0, 1, 2
0
77
Parameter write
selection
0, 1, 2
0
78
Reverse rotation
prevention selection
0, 1, 2
0
79
Operation mode
selection
0, 1, 2, 3, 4, 6, 7
0
80
Motor capacity
0.4 to 55kW,
9999
9999
81
Number of motor
poles
2, 4, 6, 8, 10, 12,
14, 16, 18, 20,
9999
9999
82
Motor excitation
current
0 to 500A,
9999
9999
Parameter
Name
Setting Range
Initial Value
83
Rated motor voltage
0 to 1000V
400V
84
Rated motor
frequency
10 to 120Hz
60Hz
89
Speed control gain
(magnetic flux vector)
0 to 200%, 9999
9999
90
Motor constant (R1)
0 to 50
Ω
,
9999
9999
91
Motor constant (R2)
9999
92
Motor constant (L1)
0 to 50
Ω
, (0 to
1000mH), 9999
9999
93
Motor constant (L2)
9999
94
Motor constant (X)
0 to 500
Ω
,
(0 to 100%),
9999
9999
95
Online auto tuning
selection
0 to 2
0
96
Auto tuning setting/
status
0, 1, 101
0
100
Adjust
able 5 point
s
V/F
V/F1 (first
frequency)
0 to 400Hz,
9999
9999
101
V/F1 (first
frequency
voltage)
0 to 1000V
0V
102
V/F2 (second
frequency)
0 to 400Hz,
9999
9999
103
V/F2 (second
frequency
voltage)
0 to 1000V
0V
104
V/F3 (third
frequency)
0 to 400Hz,
9999
9999
105
V/F3 (third
frequency
voltage)
0 to 1000V
0V
106
V/F4 (fourth
frequency)
0 to 400Hz,
9999
9999
107
V/F4 (fourth
frequency
voltage)
0 to 1000V
0V
108
V/F5 (fifth
frequency)
0 to 400Hz,
9999
9999
109
V/F5 (fifth
frequency
voltage)
0 to 1000V
0V
110
Third functions
Third
acceleration/
deceleration time
0 to 3600/360s,
9999
9999
111
Third
deceleration time
9999
112
Third torque
boost
0 to 30%, 9999
9999
113
Third V/F (base
frequency)
0 to 400Hz,
9999
9999
114
Third stall
prevention
operation current
0 to 220%
150%
115
Third stall
prevention
operation
frequency
0 to 400Hz
0
116
Third output
frequency
detection
0 to 400Hz
60Hz
117
PU communication
station number
0 to 31
0
118
PU communication
speed
48, 96, 192, 384
192
Parameter
Name
Setting Range
Initial Value