74
Engineers Forms (2/2)
Commissioning/Field settings record sheet (continued from the previous page)
Main remote controller screen
Parameters
Default
setting
Field
setting Notes
Service menu
Pump speed
Pump speed (1–5)
5
Heat source setting
Standard/Heater/Boiler/Hybrid *
7
Standard
Operation
settings
Heating operation*
8
Flow temp.range*
10
Min.temp. (25–45°C)
30°C
Max.temp. (35–60°C)
50°C
Room temp.control
*
16
Mode (Normal/Fast)
Normal
Interval (10–60 min)
10 min
Heat pump thermo
diff.adjust
ON/OFF *
6
ON
Lower limit (−9–−1°C)
−5°C
Upper limit (+3–+5°C)
5°C
Freeze stat function *
11
Outdoor ambient temp. (3–20°C) / **
5°C
Simultaneous operation (DHW/Heating)
ON/OFF *
6
OFF
Outdoor ambient temp. (−30–+10°C) *
4
−15°C
Cold weather function
ON/OFF *
6
OFF
Outdoor ambient temp. (−30–−10°C) *
4
−15°C
Boiler operation
Hybrid settings
Outdoor ambient temp.
(−30–+10°C) *
4
−15°C
Priority mode
(Ambient/Cost/CO
2)
Ambient
Intelligent set
-
tings
Energy
price
*
9
Electricity
(0.001–999 */kWh)
0.5 */kWh
Boiler
(0.001–999 */kWh)
0.5 */kWh
CO
2
emis-
sion
Electricity
(0.001–999 kg−CO2/kWh)
0.5 kg−CO2/kWh
Boiler
(0.001–999 kg−CO2/kWh)
0.5 kg−CO2/kWh
Heat
source
Heat pump capacity
(1–40 kW)
11.2
kW
Boiler efficiency
(25–150%)
80%
Booster heater 1
capacity
(0–30 kW)
2 kW
Booster heater 2
capacity
(0–30 kW)
4 kW
Floor dry up function
ON/OFF *
6
OFF
Target temp.
Start&Finish (25–60°C)
30°C
Max. temp.
(25–60°C)
45°C
Max. temp. period
(1–20 days)
5 days
Flow temp.
(Increase)
Temp. increase step (+1–+10°C) +5°C
Increase interval (1–7 days)
2 days
Flow temp.
(Decrease)
Temp. decrease step (−1–−10°C) −5°C
Decrease interval (1–7 days)
2 days
Energy
monitor
settings
Electric heater
capacity
Booster heater 1
capacity
0–30 kW
3 kW
Booster heater 2
capacity
0–30 kW
6 kW
Immersion heater
capacity
0–30 kW
0 kW
Delivered energy adjustment
−50–+50%
0%
Water pump input
Pump 1
0–200 W
*** (*
15)
Pump 2
0–200 W
0 W
Pump 3
0–200 W
0 W
Electric energy meter
0.1/1/10/100/1000 pulse/kWh
1 pulse/kWh
Heat meter
0.1/1/10/100/1000 pulse/kWh
1 pulse/kWh
External in-
put settings
Demand control (IN4)
Heat source OFF/Boiler operation
Boiler
operation
Outdoor thermostat (IN5)
Heater operation/Boiler operation
Boiler
operation
*
6
ON: the function is active; OFF: the function is inactive.
*
7
When DIP SW1-1 is set to OFF “WITHOUT Boiler” or SW2-6 is set to OFF “WITHOUT Mixing tank”, neither Boiler nor Hybrid can be selected.
*
8
Valid only when operating in Room temp. control mode.
*
9
“*” of “*/kWh” represents currency unit (e.g. € or £ or the like)
*
10
Valid only when operating in Heating room temperature.
*
11
If asterisk (**) is chosen freeze stat function is deactivated. (i.e. primary water freeze risk)
*
12
Cooling mode settings are available for ERS * model only.
*
13
Only available if DHW tank present in system.
*
14
The settings related to Zone2 can be switched only when 2-zone temperature control or 2-zone valve ON/OFF control is active.
*
15
Please change setting as follows: 180 W for Speed 5, 172 W for Speed 4, 113 W for speed 3, 70 W for Speed 2 and 38 W for Speed 1.
*
16
When DIP SW5-2 is set to OFF, the function is active.
OCH590B