42
10-4. Self diagnosis and action
Check if DIP SW is set correctly. (Refer to "6-5. DIP switch setting".)
Error code
Title and display conditions
Possible Cause
Diagnosis and action
L3
Circulation water temperature overheat
protection
<DHW/Heating/Cooling/LP/FS/OS>
Error code displayed when THW1 detects a
temp. ≥ 80ºC for 10 consecutive seconds or
THW2 detects a temp. ≥ 80ºC for 10 consecutive
seconds.
DHW : Domestic hot water mode
Heating : Heating mode
Cooling : Cooling mode
LP
: Legionella prevention mode
FS
: Freeze stat
OS
: Operation stop
TH1A/B : Room
temperature thermistor
TH2
: Liquid refrigerant temperature thermistor
THW1 : Flow water
temperature thermistor
THW2 : Return water
temperature thermistor
THW5 : Tank water
temperature thermistor
THW6 : Zone1 flow water temperature thermistor
THW7 : Zone1 return water temperature thermistor
THW8 : Zone2 flow water temperature thermistor
THW9 : Zone2 return water temperature thermistor
THWB1 : Boiler flow water temperature thermistor
THWB2 : Boiler return water temperature thermistor
1.
Insufficient system head
1.
Refer to table in "10-6. Checking Compo
-
nent Parts' Function" to determine if system
pump meets requirements.
If more head required either add an pump
of the same size or replace existing pump
with capacity model.
See "11. DISASSEMBLY PROCEDURE"
for how to replace pump.
2.
Reduced flow in primary water circuit
Due to 1 or more of the following;
Faulty pump, insufficient air purge,
blocked strainer, leak in water circuit.
2.
Check circulation pump (See "10-6. Check
-
ing Component Parts' Function" for how to
check).
Open purge valve to remove trapped air.
Check the strainer for blockages.
Check the primary water circuit for leaks.
Check that the flow amount is within the
recommended range.
3.
Valve operation fault
3. Check valves on primary water circuit are
installed level.
4. 2-way valve (local supply) actuator
fault
4.
Electrically test to determine fault.
5. 3-way valve (local supply) actuator
fault
5. 1) Electrically test to determine fault.
2) Operate 3-way valve manually using the
main remote controller. (Refer to <Manual
operation> in "9-4. Service menu".)
3) Replace 3-way valve.
6. Booster heater relay (BHC1, BHC2,
BHCP) operating fault
6. Electrically test the relays (BHC1, BHC2,
BHCP) to determine fault.
See "10-6. Checking Component Parts'
Function" for how to check.
7. Power supply voltage increase
7. Check the supply voltage.
8. THW1 or THW5 has become de
-
tached from its holder.
8.
Visually inspect location and reattach as
necessary.
9.
THW1 or THW2 fault
9.
Check resistance of thermistor against
table in "10-6. Checking Component Parts'
Function".
Compare FTC detected temperature to
hand held detector.
10. FTC board failure
10.
Replace board.
L4
Tank water temperature overheat protection
<DHW/Heating/Cooling/LP/FS/OS>
Error code display when THW5 detects a
temp. ≥ 75ºC for 10 consecutive seconds.
1.
3-way valve (local supply) actuator
fault
1.
1) Electrically test to determine fault.
2) Operate 3-way valve manually using the
main remote controller. (Refer to <Manual
operation> in "9-4. Service menu".)
3) Replace 3-way valve.
2.
Immersion heater relay (IHC) operat
-
ing fault
2.
Check immersion heater relay (IHC).
3. THW5 fault
3. Check resistance of thermistor against
table in "10-6. Checking Component Parts'
Function".
Compare FTC detected temperature to
hand held detector.
4. FTC board failure
4.
Replace board.
OCH590B