60
DISASSEMBLY PROCEDURE
PHOTOS
Photo 5-1
5. How to remove water pump/pump valve
<Water pump>
Close the pump valve and the strainer valve (OFF) before
removing the water pump, and open the valves (ON) after
reinstalling the water pump. (Photo 5-2)
(1) Remove the front panel. (Refer to Procedure 1.)
(2) Disconnect the CNP1 connector, the earth cable, and the
CNPWM connector in the control box. (Photo 5-1)
(3) Release the water pump lead wire from the 5 cable
clamps, the 2 cable straps, the coated clamp and feed
the lead wire out the control box without putting strain on
the CNP1 connector. (Photo 5-1)
(4) Swing the control box to the front. (Refer to Procedure 4.)
(5) Close (OFF) the pump valve
and the strainer valve, and
remove the G1-1/2" nuts using 2 wrenches: one to hold
the pump and the other to turn the individual nut.
Remove the water pump by sliding it horizontally. (Photo
5-2)
•
When reinstalling the G1-1/2" nuts, use a new G1-1/2"
gaskets. (Photo 5-3)
•
Set the water pump in the way that the die stamped
arrow facing down, and the terminal box facing to the
left. (Photo 5-2)
•
When opening or closing the pump valve, ensure to do
so fully, not halfway.
<Pump valve>
(6) Remove the screws fixing the pump valve stay. (Photo
5-2)
(7) Remove the pump valve by detaching the different diam
-
eter quick connection. (Photo 5-2)
•
When reinstalling the different diameter quick connection,
use a new O-ring.
•
When reinstalling the pump valve, place the handle to
the left hand side of the pump valve.
•
When opening or closing the pump valve, ensure to do
so fully, not halfway.
•
Reuse the removed pump valve stay and the pump
valve stay fixing screws. (Photo 5-4)
•
Refer to page 70 for how to attach and detach the
different diameter quick connection.
Note: Skip Steps (2) and (3) above when replacing the
pump valves only.
Photo 5-2
Photo 5-3
Pump valve
Water pump
connector (CNP1)
Earth cable
Cable
clamps
Cable strap
Lead
wire
O-ring
Photo 5-4
CNPWM
connector
Water pump
Nut (G1-1/2")
Gasket (G1-1/2")
Screws
Gasket (G1-1/2")
Terminal box
Pump valve
stay
Different diameter
quick connection
Screws
Pump valve
stay
Flow direction
Cable
clamps
Cable
clamp
Nut (G1-1/2")
Gasket (G1-1/2")
Strainer valve
OCH590B