44
Error code
Title and display conditions
Possible Cause
Diagnosis and action
L1
Booster heater overheat detection
<DHW/Heating/LP/FS/OS>
Error code displayed when THW3 detects
temp. of ≥ 85ºC for 10 consecutive seconds.
1
Insufficient system head
1
Refer to table in section 10-6. to determine
if system pump meets requirements.
If more head required either add an pump
of the same size or replace existing pump
with capacity model.
See 11. DISASSEMBLY PROCEDURE for
how to replace pump.
2
Reduced flow in primary water circuit
Due to 1 or more of the following;
Faulty pump, insufficient air purge, blocked
-
strainer, leak in water circuit.
2
Check circulation pump (See 10-6. for how
to check).
Open purge valve to remove trapped air.
Check the strainer for blockages.
Check the primary water circuit for leaks.
Check that the flow amount is within the
recommended range.
3
Valve operation fault
3
Check valves on primary water circuit are
installed level.
4
2-way valve (Locally supplied) actuator fault
4
Electrically test to determine fault.
5
3-way valve actuator fault
5
1) Electrically test to determine fault.
2) Operate 3-way valve manually using
the main remote controller. (Refer to
<Manual operation> in 9.2).
3) Replace 3-way valve coil.
4) Replace 3-way valve. (Refer to Proce
-
dure 6 in “11. DISASSEMBLY PROCE-
DURE.”
DHW : Domestic hot water mode
Heating : Heating mode
LP
: Legionella prevention mode
FS
: Freeze stat
OS
: Operation stop
TH1
: Room temp. thermistor
TH2
: Liquid refrigerant temp. thermistor
THW1 : Flow water temp. thermistor
THW2 : Return water temp. thermistor
THW3 : Booster heater temp. thermistor
THW5B : Tank water temp. thermistor
6
Booster heater relay (BHC1, BHC2, BHCP)
operating fault
6
Electrically test the relays (BHC1, BHC2,
BHCP) to determine fault.
See 10-6. for how to check
7
Power supply voltage increase
7
Check the supply voltage.
8
THW1 has become detached from its holder.
8
Visually inspect location and reattach as
necessary.
9
THW3 fault
9
Check resistance of thermistor against table
in section 10-6.
Compare FTC3 detected temperature to
hand held detector.
0
FTC3 board failure
0
Replace board.
L
Booster heater thermistor (THW3) failure
<DHW/Heating/LP/FS>
Error code displayed when THW3 is at open
(≤ 1.31ºC) or short (≥ 219.42ºC).
Exceptions
Error code will not be displayed if;
During defrost and 10 mins after defrost
operation,
For 10 mins after pump1 is switched on,
When THW1 < 10deg.
1
Connector/terminal wire has become
detached or loose wiring.
1
Visually check the terminals and connections
and reattach as appropriate.
2
THW3 fault
2
Check resistance of thermistor against table
in section 10-6.
Compare FTC3 detected temperature to
hand held detector.
3
FTC3 board failure
3
Replace board.
10-4. Self diagnosis and action
Check if Dip SW is set correctly. (Refer to Chapter 6-10.)
Summary of Contents for EHPT20X-VM2HA
Page 11: ... See Chapter 6 10 11 6 WIRING DIAGRAM 6 1 EHST20C VM6HA ...
Page 12: ... See Chapter 6 10 12 6 2 EHST20C YM9HA ...
Page 13: ... See Chapter 6 10 13 6 3 EHST20C VM6A EHST20C VM6SA ...
Page 14: ... See Chapter 6 10 14 6 4 EHST20C YM9A ...
Page 15: ... See Chapter 6 10 15 6 5 EHPT20X VM2HA ...
Page 16: ... See Chapter 6 10 16 6 6 EHPT20X VM6HA ...
Page 17: ... See Chapter 6 10 17 6 7 EHPT20X YM9HA ...
Page 18: ... See Chapter 6 10 18 6 8 EHPT20X VM6A ...
Page 19: ... See Chapter 6 10 19 6 9 EHPT20X YM9A ...
Page 25: ...25 WATER SYSTEM DIAGRAM 8 EHST20C M HA M A EHST20C VM6SA ...
Page 26: ...26 EHPT20X VM2HA EHPT20X M HA M A ...
Page 75: ...75 ...