CAUTION (SPLIT MODELS ONLY)
<Using R410A refrigerant heat pumps>
Use C1220 copper phosphorus, for copper and copper alloy seamless pipes, to connect the refrigerant pipes. Make sure the insides of the pipes are clean and
do not contain any harmful contaminants such as sulfuric compounds, oxidants, debris, or dust. Use pipes with the specified thickness. Note the following if reus
-
ing existing pipes that carried R22 refrigerant.
- Replace the existing flare nuts and flare the flared sections again.
- Do not use thin pipes.
Store the pipes to be used during installation indoors and keep both ends of the pipes sealed until just before brazing. (Leave elbow joints, etc. in their packag
-
ing.) If dust, debris, or moisture enters the refrigerant lines, oil deterioration or compressor breakdown may result.
Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil applied to the flared sections. If mineral oil is mixed in the refrigeration oil, oil dete
-
rioration may result.
Do not use refrigerant other than R410A refrigerant. If another refrigerant is used, the chlorine will cause the oil to deteriorate.
Use the following tools specifically designed for use with R410A refrigerant. The following tools are necessary to use R410A refrigerant. Contact your nearest
dealer for any questions.
Tools (for R410A)
Gauge manifold
Flare tool
Charge hose
Size adjustment gauge
Gas leak detector
Vacuum pump adapter
Torque wrench
Electronic refrigerant charging scale
Be sure to use the correct tools. If dust, debris, or moisture enters the refrigerant lines, refrigeration oil deterioration may result.
Do not use a charging cylinder. If a charging cylinder is used, the composition of the refrigerant will change and system efficiency will be reduced.
WARNING (SPLIT MODELS ONLY)
Do not discharge refrigerant into the atmosphere. If refrigerant leaks during installation, ventilate the room.
Use appropriate tools for high pressure refrigerant.
When pumping down refrigerant , stop the compressor before disconnecting the refrigerant pipes.
During installation securely fasten the refrigerant pipes before starting the compressor.
Check that refrigerant gas does not leak after the completion of installation.
Use R410A refrigerant only. Do not allow air to enter the lines. Failure to observe these instructions will cause mechanical failure, system failure or, in the worst
case, serious breach of product safety.
Summary of Contents for EHPT20X-VM2HA
Page 11: ... See Chapter 6 10 11 6 WIRING DIAGRAM 6 1 EHST20C VM6HA ...
Page 12: ... See Chapter 6 10 12 6 2 EHST20C YM9HA ...
Page 13: ... See Chapter 6 10 13 6 3 EHST20C VM6A EHST20C VM6SA ...
Page 14: ... See Chapter 6 10 14 6 4 EHST20C YM9A ...
Page 15: ... See Chapter 6 10 15 6 5 EHPT20X VM2HA ...
Page 16: ... See Chapter 6 10 16 6 6 EHPT20X VM6HA ...
Page 17: ... See Chapter 6 10 17 6 7 EHPT20X YM9HA ...
Page 18: ... See Chapter 6 10 18 6 8 EHPT20X VM6A ...
Page 19: ... See Chapter 6 10 19 6 9 EHPT20X YM9A ...
Page 25: ...25 WATER SYSTEM DIAGRAM 8 EHST20C M HA M A EHST20C VM6SA ...
Page 26: ...26 EHPT20X VM2HA EHPT20X M HA M A ...
Page 75: ...75 ...