<Emergency operation>
In Emergency operation mode the outdoor heat pump unit will not operate. Heat
-
ing for DHW and space heating is provided by the booster heater and the tank
immersion heater (if installed). Space heating flow temp is restricted 40°C if an
immersion heater is not present on the DHW tank then the booster heater will
also indirectly heat the DHW.
When in Emergency operation the main control has NO control functions. It's only
function is to display the Main screen and Information screen by pressing F1, all
other buttons are disabled.
• Activating Emergency operation mode
To activate Emergency operation see the following:
Switch OFF the breaker for the outdoor unit (or both breakers if cylinder pow
-
ered independently).
Change DIP switch SW4-5 to ON.
Switch ON the breaker(s).
Emergency Operation is now activated.
• Deactivating Emergency operation mode
To deactivate Emergency operation see the following:
Switch OFF the breaker for the outdoor unit (or both breakers if cylinder pow
-
ered independently).
Change DIP switch SW4-5 to OFF.
Switch ON the breaker(s).
Emergency operation is now deactivated.
WARNING
Do not attempt to change the DIP switches whilst the breaker(s) are ON as
this could result in ELECTROCUTION.
1.
.
3.
4.
1.
.
3.
4.
Summary of Contents for EHPT20X-VM2HA
Page 11: ... See Chapter 6 10 11 6 WIRING DIAGRAM 6 1 EHST20C VM6HA ...
Page 12: ... See Chapter 6 10 12 6 2 EHST20C YM9HA ...
Page 13: ... See Chapter 6 10 13 6 3 EHST20C VM6A EHST20C VM6SA ...
Page 14: ... See Chapter 6 10 14 6 4 EHST20C YM9A ...
Page 15: ... See Chapter 6 10 15 6 5 EHPT20X VM2HA ...
Page 16: ... See Chapter 6 10 16 6 6 EHPT20X VM6HA ...
Page 17: ... See Chapter 6 10 17 6 7 EHPT20X YM9HA ...
Page 18: ... See Chapter 6 10 18 6 8 EHPT20X VM6A ...
Page 19: ... See Chapter 6 10 19 6 9 EHPT20X YM9A ...
Page 25: ...25 WATER SYSTEM DIAGRAM 8 EHST20C M HA M A EHST20C VM6SA ...
Page 26: ...26 EHPT20X VM2HA EHPT20X M HA M A ...
Page 75: ...75 ...