4. Electrical work

4.1. Indoor unit (Fig. 4-1)

1.Remove 2 screws to detach the electric component cover.
2.Route each cable through the wiring intake into the electric component box. (Pro-

cure power supply cable and control cable locally.)

3.Securely connect the power supply cable and control cable to the terminal blocks.
4.Secure the cables with clamps outside the electric component box.
5.Attach the electric component cover as it was.
• Do not allow slackening of the terminal screws.
• Always install earth.

(Earth cable dia: Thicker than 1.6 mm)

• Fix power supply cable and control cable to electric component box by using buffer

bushing for tensile forse. (PG connection or the like.)

s

s

s

s

s

Selecting non-fuse breaker (NF) or earth leakage breaker (NV).

A means for the disconnection of the supply with an isolation switch, or similar de-
vice, in all active conductors shall be incorporated in the fixed wiring.

Power supply wiring

• Power supply codes of appliance shall not be lighter than design 245 IEC 53 or 227

IEC 53.

• A switch with at least 3 mm contact separation in each pole shall be provided by the

air conditioner installation.

Power cable size: more than 1.5 mm

2

.

Fig. 4-1

Fig. 4-2

1

2

A

A

C

TB5

TB15 TB5

TB15

S

M1 M2

S

M1 M2

B

TB3

M1 M2

2

1

C

2

1

A

A

C

TB5

TB5

S

M1 M2

S

M1 M2

C

B

TB3

M1 M2

4.2. Connecting remote controller, indoor and outdoor

transmission cables (Fig. 4-2)

• Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire)

The “S” on indoor unit TB5 is a shielding wire connection. For specifications about
the connecting cables, refer to the outdoor unit installation manual.

• Install a remote controller following the manual supplied with the remote controller.
• Connect the remote controller’s transmission cable within 10 m using a 0.75 mm

2

core cable. If the distance is more than 10 m, use a 1.25 mm

2

 junction cable.

1

MA Remote controller

• Connect the “1” and “2” on indoor unit TB15 to a MA remote controller. (Non-polar-

ized 2-wire)

• DC 9 to 13 V between 1 and 2 (MA remote controller)

2

M-NET Remote controller

• Connect the “M1” and “M2” on indoor unit TB5 to a M-NET remote controller. (Non-

polarized 2-wire)

• DC 24 to 30 V between M1 and M2 (M-NET remote controller)

A

Terminal block for indoor transmission cable

B

Terminal block for outdoor transmission cable

C

Remote controller

Constraints on transmission cable (Fig. 4-3)

Longest wiring length (L

1

+L

2

+L

4

 or L

1

+L

3

 or L

2

+L

3

+L

4

): less than 200 m

Length between indoor unit and remote controller (

R

): within 10 m

G

Outdoor unit

H

Earth

I

BC controller

J

Indoor unit

K

M-NET Remote controller

L

Non-polarized 2-wire

Note:
*1 Put the transmission cable earth via the outdoor unit’s earth terminal 

 to

the ground.

*2 If the remote controller cable exceeds 10 m, use a 1.25 mm

2

 diameter cable

over the exceeded portion, and add that exceeded portion to within 200 m.

*3 The BC controller is required only for simultaneous cooling and heating

series R2.

4.3. Setting addresses (Fig. 4-4)

(Be sure to operate with the main power turned OFF.)
• There are two types of rotary switch setting available: setting addresses 1 to 9 and

over 10, and setting branch numbers.

Fig. 4-3

Fig. 4-4

G

I

J

J

J

K

K

K

K

J

J

L

K

H

*1

*3

L1

L2

L4

r

L3

*2

A

Electric component cover

B

Electric component box

C

Entry for power supply cable

D

Entry for control cable

E

Cable clamp

F

Power supply terminals

G

Transmission terminals

H

MA Remoto controller terminal

I

Indoor controller

J

Power board

123456

ON

OFF

ON

OFF

SW1

SW2

SW3

SW4

12345

ON

OFF

12345678910

12345678910

SW11

0

SW12

0

SW14

0

CONNECTION
No.

3RD
DIGIT

2ND
DIGIT

1ST
DIGIT

Summary of Contents for CITY MULTI PLFY-P-VCM-E

Page 1: ... ÛË Ú Î ÏÂ ÛÙÂ È ÛÂÙÂ ÚÔÛÂ ÙÈÎ Ùfi ÙÔ ÂÁ ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÚÈÓ Ú ÛÂÙÂ ÙËÓ ÂÁÎ Ù ÛÙ ÛË ÙË ÌÔÓ ÎÏÈÌ ÙÈÛÌÔ MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado MONTAJ ELK TABI Emniyetli ve do ru biçimde nas l kullan laca n ö renmek için lütfen klima cihaz n monte etmeden önce bu elkitab n dikkatle okuyunuz...

Page 2: ...pipe 4 4 Electrical work 6 5 Installing the grille 7 6 Test run Fig 6 1 9 1 Safety precautions Indicates an action that must be avoided Indicates that important instructions must be followed Indicates a part which must be grounded Indicates that caution should be taken with rotating parts Indicates that the main switch must be turned off before servicing Beware of electric shock Beware of hot surf...

Page 3: ...ch inner diameter fits into the outer diamete of the duct flange In case that the environment above the ceiling is high temperature and high humid ity wrap the duct in a heat insulate to avoid causing dew drop on the wall A Duct flange recommended shape Thickness 0 8 or more B 3 ø5 hole C Detail drawing of fresh air intake D Indoor unit E Ceiling surface F 3 ø2 8 Burring hole G ø73 4 cutout hole H...

Page 4: ...on bolts Fig 2 7 Using the gauge attached to the grille ensure that the bottom of the main unit is properly aligned with the opening of the ceiling Be sure to confirm this otherwise condensation may form and drip due to air leakage etc Confirm that the main unit is horizontally levelled using a level or a vinyl tube filled with water After checking the position of the main unit tighten the nuts of...

Page 5: ...ening torque Flare nut O D Liquid Gas pipe pipe mm mm 17 26 22 29 22 29 22 36 C Apply refrigerating machine oil over the entire flare seat surface Use the provided flare nut for the following pipes Liquid pipe of P50 P100 P125 and gas pipe of P50 R410A Liquid pipe Gas pipe Tightening Tightening Pipe size torque Pipe size torque mm N m mm N m ODø6 35 1 4 14 18 ODø12 7 1 2 49 61 ODø6 35 1 4 34 42 OD...

Page 6: ...ler Connect the remote controller s transmission cable within 10 m using a 0 75 mm2 core cable If the distance is more than 10 m use a 1 25 mm2 junction cable 1 MA Remote controller Connect the 1 and 2 on indoor unit TB15 to a MA remote controller Non polar ized 2 wire DC 9 to 13 V between 1 and 2 MA remote controller 2 M NET Remote controller Connect the M1 and M2 on indoor unit TB5 to a M NET re...

Page 7: ...5 1 1 4 5 2 3 Fig 5 3 B A C 1 1 D E 2 F G F B 1 Fig 5 4 5 2 Preparing to attach the grille Fig 5 2 With the gauge supplied with this kit adjust and check the positioning of the unit relative to the ceiling If the unit is not properly positioned in the ceiling there may be air leaks condensation may form or the up down vanes may not operate cor rectly Make sure that the opening in the ceiling is wi...

Page 8: ...ng to the preference of the customer The operation of the fixed up down vanes and all automatic controls cannot be performed using the remote controller In addition the actual position of the vanes may differ from the position indicated on the remote controller 1 Turn off the main power switch Injuries and or an electrical shock may occur while the fan of the unit is rotating 2 Disconnect the conn...

Page 9: ...nstallation in a new premises 1 Remove the cover of the water supply inlet and add about 1000 cc of water using a water supply pump etc During this process be careful not to spray water into the drain pump mechanism 2 Confirm that water is being drained out through the drainage outlet after switch ing over from remote control mode to trial run mode 3 After checking the drainage ensure that the cov...

Page 10: ...EC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Thailand BG79U363H01 The product at hand is based on the following EU regulations ...

Reviews: