2.2. Ceiling openings and suspension bolt installation

locations (Fig. 2-2)

• Using the installation template (top of the package) and the gauge (supplied as an

accessory with the grille), make an opening in the ceiling so that the main unit can
be installed as shown in the diagram. (The method for using the template and the
gauge are shown.)

* Before using, check the dimensions of template and gauge, because they change

due to fluctuations of temperature and humidity.

* The dimensions of ceiling opening can be regulated within the range shown in

following diagram; so center the main unit against the opening of ceiling, ensur-
ing that the respective opposite sides on all sides of the clearance between
them becomes identical.

• Use M10 (3/8") suspension bolts.

* Suspension bolts are to be procured at the field.

• Install securely, ensuring that there is no clearance between the ceiling panel &

grille, and between the main unit & grille.

2. Installing the indoor unit

A

Outer side of main unit

B

Bolt pitch

C

Ceiling opening

D

Outer side of Grille

E

Grille

F

Ceiling

G

Min. 500 mm (Entire periphery)

If setting the maintenance space for 

G

, be

sure to leave is a minimum of 700 mm.

H

Maintenance space

I

Fresh air intake

J

Angle

K

Electric component box

*

Note that the space between ceiling panel of the unit and ceiling slab and etc must be 10 to
15 mm to be left.

*

Leave the maintenance space at the electric component box end.

2.3. Installation of duct (in case of fresh air intake)

(Fig. 2-3)

 Caution:

Linkage of duct fan and air conditioner
ln case that a duct fan is used, be sure to make it linked with the air conditioner
when outside air is taken.
Do not run the duct fan only. It can cause dew drop.

Making a duct flange (prepared locally)

• The shape of duct flange shown left is recommended.

Installation of duct flange

• Cut out the cutout hole. Do not knock it out.
• Install a duct flange to the cutout hole of the indoor unit with three 4 

×

 10 tapping

screws which should be prepared locally.

Installation of duct (should be prepared locally)

• Prepare a duct of which inner diameter fits into the outer diamete of the duct flange.
• In case that the environment above the ceiling is high temperature and high humid-

ity, wrap the duct in a heat insulate to avoid causing dew drop on the wall.

A

Duct flange recommended shape

(Thickness:0.8 or more)

B

3-ø5 hole

C

Detail drawing of fresh air intake

D

Indoor unit

E

Ceiling surface

F

3-ø2.8 Burring hole

G

ø73.4 cutout hole

H

Duct flange (Prepared locally)

I

×

 10 Tapping screw (Prepared locally)

J

Duct

2.4. Suspension structure (Give site of suspension

strong structure) (Fig. 2-4)

• The ceiling work differs according to the construction of the building. Buidling con-

structors and interior decorators should be consulted for details.

(1) Extent of ceiling removal: The ceiling must be kept completely horizontal and the

ceiling foundation (framework: wooden slats and slat holders) must be reinforced
in order to protect the ceiling from vibration.

(2) Cut and remove the ceiling foundation.
(3) Reinforce the ends of the ceiling foundation where it has been cut and add ceiling

foundation for securing the ends of the ceiling board.

(4) When installing the unit on a slanting ceiling, interlock a pillow between the ceiling

and the grille and set so that the unit is installed horizontally.

1

Wooden structures

• Use tie beams (single storied houses) or second floor beams (two story houses) as

reinforcing members.

• Wooden beams for suspending air conditioners must be sturdy and their sides

must be at least 6 cm long if the beams are separated by not more than 90 cm and
their sides must be at least 9 cm long if the beams are separated by as much as
180 cm. The size of the suspension bolts should be ø10 (3/8"). (The bolts do not
come with the unit.)

2

Ferro-concrete structures

Secure the suspension bolts using the method shown, or use steel or wooden hang-
ers, etc. to install the suspension bolts.

A

Unit

B

Grille

C

Pillow

D

Ceiling

E

Rafter

F

Beam

G

Roof beam

H

Use inserts rated at 100-150 kg
each (procure locally)

I

Suspension bolts M10 (3/8") (procure
locally)

J

Steel reinforcing rod

A

B

C

J

H

I

D

E

F G

*B

*B

1

2

Fig. 2-4

Fig. 2-2

B

30

120

120

20

75

100

70

15

G

E

D

F

120

120

92

25

     

+5

27

 

  

0

208

100

Fig. 2-3

D

H

I

J

A

(mm)

C

(mm)

*B: Suspension bolt pitch (see Fig. 2-2 

B

 for details)

Summary of Contents for CITY MULTI PLFY-P-VCM-E

Page 1: ... ÛË Ú Î ÏÂ ÛÙÂ È ÛÂÙÂ ÚÔÛÂ ÙÈÎ Ùfi ÙÔ ÂÁ ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÚÈÓ Ú ÛÂÙÂ ÙËÓ ÂÁÎ Ù ÛÙ ÛË ÙË ÌÔÓ ÎÏÈÌ ÙÈÛÌÔ MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado MONTAJ ELK TABI Emniyetli ve do ru biçimde nas l kullan laca n ö renmek için lütfen klima cihaz n monte etmeden önce bu elkitab n dikkatle okuyunuz...

Page 2: ...pipe 4 4 Electrical work 6 5 Installing the grille 7 6 Test run Fig 6 1 9 1 Safety precautions Indicates an action that must be avoided Indicates that important instructions must be followed Indicates a part which must be grounded Indicates that caution should be taken with rotating parts Indicates that the main switch must be turned off before servicing Beware of electric shock Beware of hot surf...

Page 3: ...ch inner diameter fits into the outer diamete of the duct flange In case that the environment above the ceiling is high temperature and high humid ity wrap the duct in a heat insulate to avoid causing dew drop on the wall A Duct flange recommended shape Thickness 0 8 or more B 3 ø5 hole C Detail drawing of fresh air intake D Indoor unit E Ceiling surface F 3 ø2 8 Burring hole G ø73 4 cutout hole H...

Page 4: ...on bolts Fig 2 7 Using the gauge attached to the grille ensure that the bottom of the main unit is properly aligned with the opening of the ceiling Be sure to confirm this otherwise condensation may form and drip due to air leakage etc Confirm that the main unit is horizontally levelled using a level or a vinyl tube filled with water After checking the position of the main unit tighten the nuts of...

Page 5: ...ening torque Flare nut O D Liquid Gas pipe pipe mm mm 17 26 22 29 22 29 22 36 C Apply refrigerating machine oil over the entire flare seat surface Use the provided flare nut for the following pipes Liquid pipe of P50 P100 P125 and gas pipe of P50 R410A Liquid pipe Gas pipe Tightening Tightening Pipe size torque Pipe size torque mm N m mm N m ODø6 35 1 4 14 18 ODø12 7 1 2 49 61 ODø6 35 1 4 34 42 OD...

Page 6: ...ler Connect the remote controller s transmission cable within 10 m using a 0 75 mm2 core cable If the distance is more than 10 m use a 1 25 mm2 junction cable 1 MA Remote controller Connect the 1 and 2 on indoor unit TB15 to a MA remote controller Non polar ized 2 wire DC 9 to 13 V between 1 and 2 MA remote controller 2 M NET Remote controller Connect the M1 and M2 on indoor unit TB5 to a M NET re...

Page 7: ...5 1 1 4 5 2 3 Fig 5 3 B A C 1 1 D E 2 F G F B 1 Fig 5 4 5 2 Preparing to attach the grille Fig 5 2 With the gauge supplied with this kit adjust and check the positioning of the unit relative to the ceiling If the unit is not properly positioned in the ceiling there may be air leaks condensation may form or the up down vanes may not operate cor rectly Make sure that the opening in the ceiling is wi...

Page 8: ...ng to the preference of the customer The operation of the fixed up down vanes and all automatic controls cannot be performed using the remote controller In addition the actual position of the vanes may differ from the position indicated on the remote controller 1 Turn off the main power switch Injuries and or an electrical shock may occur while the fan of the unit is rotating 2 Disconnect the conn...

Page 9: ...nstallation in a new premises 1 Remove the cover of the water supply inlet and add about 1000 cc of water using a water supply pump etc During this process be careful not to spray water into the drain pump mechanism 2 Confirm that water is being drained out through the drainage outlet after switch ing over from remote control mode to trial run mode 3 After checking the drainage ensure that the cov...

Page 10: ...EC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Thailand BG79U363H01 The product at hand is based on the following EU regulations ...

Reviews: