2

s

Before installing the unit, make sure you read all the “Safety precau-
tions”.

s

Please report to your supply authority or obtain their consent before
connecting this equipment to the power supply system.

 Warning:

Describes precautions that must be observed to prevent danger of injury or
death to the user.

 Caution:

Describes precautions that must be observed to prevent damage to the unit.

After installation work has been completed, explain the “Safety Precautions,” use,
and maintenance of the unit to the customer according to the information in the Op-
eration Manual and perform the test run to ensure normal operation. Both the Instal-
lation Manual and Operation Manual must be given to the user for keeping. These
manuals must be passed on to subsequent users.

Contents

 Warning:

• Ask the dealer or an authorized technician to install the air conditioner.
• Install the unit at a place that can withstand its weight.
• Use the specified cables for wiring.
• Use only accessories authorized by Mitsubishi Electric and ask the dealer or

an authorized technician to install them.

• Do not touch the heat exchanger fins.
• Install the air conditioner according to this Installation Manual.

• Have all electric work done by a licensed electrician according to local regu-

lations.

• If the air conditioner is installed in a small room, measures must be taken to

prevent the refrigerant concentration from exceeding the safety limit even if
the refrigerant should leak.

• The cut face punched parts may cause injury by cut, etc. The installers are

requested to wear protective equipement such as gloves, etc.

1. Safety precautions ................................................................................... 2
2. Installing the indoor unit ........................................................................... 2
3. Refrigerant pipe and drain pipe ............................................................... 4

4. Electrical work .......................................................................................... 6
5. Installing the grille .................................................................................... 7
6. Test run (Fig. 6-1) ..................................................................................... 9

1. Safety precautions

: Indicates an action that must be avoided.

: Indicates that important instructions must be followed.

: Indicates a part which must be grounded.

: Indicates that caution should be taken with rotating parts.

: Indicates that the main switch must be turned off before servicing.

: Beware of electric shock.

: Beware of hot surface.

ELV

: At servicing, please shut down the power supply for both the Indoor and

Outdoor Unit.

 Warning:

Carefully read the labels affixed to the main unit.

 Caution:

• Do not use the existing refrigerant piping, when use R410A or R407C refrig-

erant.

• Use ester oil, either oil or alkylbenzene (small amount) as the refrigerator oil

to coat flares and flange connections, when use R410A or R407C refrigerant.

• Do not use the air conditioner where food, pets, plants, precision instruments,

or artwork are kept.

• Do not use the air conditioner in special environments.
• Ground the unit.

• Install an leak circuit breaker, as required.
• Use power line cables of sufficient current carrying capacity and rating.
• Use only a circuit breaker and fuse of the specified capacity.
• Do not touch the switches with wet fingers.
• Do not touch the refrigerant pipes during and immediately after operation.
• Do not operate the air conditioner with the panels and guards removed.
• Do not turn off the power immediately after stopping operation.

2. Installing the indoor unit

2.1. Check the indoor unit accessories (Fig. 2-1)

The indoor unit should be supplied with the following accessories.

Accessory name

Q’ty

1

Installation template

1

2

Washers (with insulation)

4

Washers (without insulation)

4

3

Pipe cover (for refrigerant piping joint)
small diameter (liquid)

1

large diameter (gas)

1

4

Band (large)

6

Band (small)

2

5

Screw with washer (M5 

×

 25) for mounting grille

4

6

Drain socket

1

7

Insulation

1

Fig. 2-1

1

2

3

4

6

5

7

Summary of Contents for CITY MULTI PLFY-P-VCM-E

Page 1: ... ÛË Ú Î ÏÂ ÛÙÂ È ÛÂÙÂ ÚÔÛÂ ÙÈÎ Ùfi ÙÔ ÂÁ ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÚÈÓ Ú ÛÂÙÂ ÙËÓ ÂÁÎ Ù ÛÙ ÛË ÙË ÌÔÓ ÎÏÈÌ ÙÈÛÌÔ MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado MONTAJ ELK TABI Emniyetli ve do ru biçimde nas l kullan laca n ö renmek için lütfen klima cihaz n monte etmeden önce bu elkitab n dikkatle okuyunuz...

Page 2: ...pipe 4 4 Electrical work 6 5 Installing the grille 7 6 Test run Fig 6 1 9 1 Safety precautions Indicates an action that must be avoided Indicates that important instructions must be followed Indicates a part which must be grounded Indicates that caution should be taken with rotating parts Indicates that the main switch must be turned off before servicing Beware of electric shock Beware of hot surf...

Page 3: ...ch inner diameter fits into the outer diamete of the duct flange In case that the environment above the ceiling is high temperature and high humid ity wrap the duct in a heat insulate to avoid causing dew drop on the wall A Duct flange recommended shape Thickness 0 8 or more B 3 ø5 hole C Detail drawing of fresh air intake D Indoor unit E Ceiling surface F 3 ø2 8 Burring hole G ø73 4 cutout hole H...

Page 4: ...on bolts Fig 2 7 Using the gauge attached to the grille ensure that the bottom of the main unit is properly aligned with the opening of the ceiling Be sure to confirm this otherwise condensation may form and drip due to air leakage etc Confirm that the main unit is horizontally levelled using a level or a vinyl tube filled with water After checking the position of the main unit tighten the nuts of...

Page 5: ...ening torque Flare nut O D Liquid Gas pipe pipe mm mm 17 26 22 29 22 29 22 36 C Apply refrigerating machine oil over the entire flare seat surface Use the provided flare nut for the following pipes Liquid pipe of P50 P100 P125 and gas pipe of P50 R410A Liquid pipe Gas pipe Tightening Tightening Pipe size torque Pipe size torque mm N m mm N m ODø6 35 1 4 14 18 ODø12 7 1 2 49 61 ODø6 35 1 4 34 42 OD...

Page 6: ...ler Connect the remote controller s transmission cable within 10 m using a 0 75 mm2 core cable If the distance is more than 10 m use a 1 25 mm2 junction cable 1 MA Remote controller Connect the 1 and 2 on indoor unit TB15 to a MA remote controller Non polar ized 2 wire DC 9 to 13 V between 1 and 2 MA remote controller 2 M NET Remote controller Connect the M1 and M2 on indoor unit TB5 to a M NET re...

Page 7: ...5 1 1 4 5 2 3 Fig 5 3 B A C 1 1 D E 2 F G F B 1 Fig 5 4 5 2 Preparing to attach the grille Fig 5 2 With the gauge supplied with this kit adjust and check the positioning of the unit relative to the ceiling If the unit is not properly positioned in the ceiling there may be air leaks condensation may form or the up down vanes may not operate cor rectly Make sure that the opening in the ceiling is wi...

Page 8: ...ng to the preference of the customer The operation of the fixed up down vanes and all automatic controls cannot be performed using the remote controller In addition the actual position of the vanes may differ from the position indicated on the remote controller 1 Turn off the main power switch Injuries and or an electrical shock may occur while the fan of the unit is rotating 2 Disconnect the conn...

Page 9: ...nstallation in a new premises 1 Remove the cover of the water supply inlet and add about 1000 cc of water using a water supply pump etc During this process be careful not to spray water into the drain pump mechanism 2 Confirm that water is being drained out through the drainage outlet after switch ing over from remote control mode to trial run mode 3 After checking the drainage ensure that the cov...

Page 10: ...EC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Thailand BG79U363H01 The product at hand is based on the following EU regulations ...

Reviews: