5.3. Installing the grille

• Please pay attention because there is a restriction in the attachment position of the

grille.

5.3.1. Preparations (Fig. 5-5)

• Install the two enclosed screws with washer in the main unit (at the corner refriger-

ant pipe area and at the opposite corner) as shown in the diagram.

A

Main unit

B

Detailed diagram of installed screw with washer (accessory).

15~20

A

B

(mm)

Fig. 5-5

5.3.2. Temporary installation of the grille (Fig. 5-6)

• Align the electric component box of the main unit and the receiver of the grille, and

then temporarily secure the grille using the bell shaped holes.

* Make sure that the lead wiring of the grille does not get pinched between the

grille and the main unit.

A

Main unit

B

Electric component box

C

Screw with washer (for temporary use)

D

Screw with washer (Accessory)

E

Grille

F

Bell shaped hole

5.3.3. Securing the grille (Fig. 5-7)

• Secure the grille to the main unit by tightening the previously installed two screws

(with captive washer) as well as the two remaining screws (with captive washer).

* Make sure that there are no gaps between the main unit and the grille or the

grille and the ceiling.

A

Ceiling

B

Main unit

C

Grille

D

Make sure that there are no gaps.

A

C

D

B

Fig. 5-6

Fig. 5-7

5. Installing the grille

C

D

B

E

Fig. 5-8

5.4. Locking the up/down airflow direction (Fig. 5-9)

The vanes of the unit can be set and locked in up or down orientations depending
upon the environment of use.
• Set according to the preference of the customer.

The operation of the fixed up/down vanes and all automatic controls cannot be
performed using the remote controller. In addition, the actual position of the vanes
may differ from the position indicated on the remote controller.

1

Turn off the main power switch.
Injuries and or an electrical shock may occur while the fan of the unit is rotating.

2

Disconnect the connector for the vane motor of the vent that you want to lock.
(While pressing the button, remove the connector in the direction indicated by the
arrow as shown in the diagram.) After removing the connector, insulate it with
tape.

3

To adjust the desired airflow direction, slowly move the up/down vanes within the
specified range. (Fig. 5-10)

Specified range

Up/down airflow

Horizontal 30° Downward 45° Downward 55° Downward 70°

direction

A (mm)

21

25

28

30

• The vanes can be set between 21 and 30 mm.

 Caution:

Do not set the up/down vanes passed the specified range. Condensation could
form on and drop from the ceiling, or the unit could malfunction.

C

B

A

D

B

A

D

Fig. 5-9

A

Button

B

Vane motor

C

Up/down vanes

D

Connector

E

F

A

5.3.4. Wire connection (Fig. 5-8)

• Be sure to connect the unit to the connector (white:10-pole/red:9-pole). Next, at-

tach the white glass tube that comes with the main unit so that the tube covers the
connector. Close the opening of the glass tube with the band.

• Make sure that there is no slack in the each lead wire at the fastener on the grille.

A

Fastener (Accessory)

B

White glass tube

C

Connector of the main unit

D

Connector of the grille

E

Band (Accessory)

E

 Measurement standard

position of grille

F

 Up/down vanes

Fig. 5-10

Summary of Contents for CITY MULTI PLFY-P-VCM-E

Page 1: ... ÛË Ú Î ÏÂ ÛÙÂ È ÛÂÙÂ ÚÔÛÂ ÙÈÎ Ùfi ÙÔ ÂÁ ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÚÈÓ Ú ÛÂÙÂ ÙËÓ ÂÁÎ Ù ÛÙ ÛË ÙË ÌÔÓ ÎÏÈÌ ÙÈÛÌÔ MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado MONTAJ ELK TABI Emniyetli ve do ru biçimde nas l kullan laca n ö renmek için lütfen klima cihaz n monte etmeden önce bu elkitab n dikkatle okuyunuz...

Page 2: ...pipe 4 4 Electrical work 6 5 Installing the grille 7 6 Test run Fig 6 1 9 1 Safety precautions Indicates an action that must be avoided Indicates that important instructions must be followed Indicates a part which must be grounded Indicates that caution should be taken with rotating parts Indicates that the main switch must be turned off before servicing Beware of electric shock Beware of hot surf...

Page 3: ...ch inner diameter fits into the outer diamete of the duct flange In case that the environment above the ceiling is high temperature and high humid ity wrap the duct in a heat insulate to avoid causing dew drop on the wall A Duct flange recommended shape Thickness 0 8 or more B 3 ø5 hole C Detail drawing of fresh air intake D Indoor unit E Ceiling surface F 3 ø2 8 Burring hole G ø73 4 cutout hole H...

Page 4: ...on bolts Fig 2 7 Using the gauge attached to the grille ensure that the bottom of the main unit is properly aligned with the opening of the ceiling Be sure to confirm this otherwise condensation may form and drip due to air leakage etc Confirm that the main unit is horizontally levelled using a level or a vinyl tube filled with water After checking the position of the main unit tighten the nuts of...

Page 5: ...ening torque Flare nut O D Liquid Gas pipe pipe mm mm 17 26 22 29 22 29 22 36 C Apply refrigerating machine oil over the entire flare seat surface Use the provided flare nut for the following pipes Liquid pipe of P50 P100 P125 and gas pipe of P50 R410A Liquid pipe Gas pipe Tightening Tightening Pipe size torque Pipe size torque mm N m mm N m ODø6 35 1 4 14 18 ODø12 7 1 2 49 61 ODø6 35 1 4 34 42 OD...

Page 6: ...ler Connect the remote controller s transmission cable within 10 m using a 0 75 mm2 core cable If the distance is more than 10 m use a 1 25 mm2 junction cable 1 MA Remote controller Connect the 1 and 2 on indoor unit TB15 to a MA remote controller Non polar ized 2 wire DC 9 to 13 V between 1 and 2 MA remote controller 2 M NET Remote controller Connect the M1 and M2 on indoor unit TB5 to a M NET re...

Page 7: ...5 1 1 4 5 2 3 Fig 5 3 B A C 1 1 D E 2 F G F B 1 Fig 5 4 5 2 Preparing to attach the grille Fig 5 2 With the gauge supplied with this kit adjust and check the positioning of the unit relative to the ceiling If the unit is not properly positioned in the ceiling there may be air leaks condensation may form or the up down vanes may not operate cor rectly Make sure that the opening in the ceiling is wi...

Page 8: ...ng to the preference of the customer The operation of the fixed up down vanes and all automatic controls cannot be performed using the remote controller In addition the actual position of the vanes may differ from the position indicated on the remote controller 1 Turn off the main power switch Injuries and or an electrical shock may occur while the fan of the unit is rotating 2 Disconnect the conn...

Page 9: ...nstallation in a new premises 1 Remove the cover of the water supply inlet and add about 1000 cc of water using a water supply pump etc During this process be careful not to spray water into the drain pump mechanism 2 Confirm that water is being drained out through the drainage outlet after switch ing over from remote control mode to trial run mode 3 After checking the drainage ensure that the cov...

Page 10: ...EC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Thailand BG79U363H01 The product at hand is based on the following EU regulations ...

Reviews: