31
OCH728A
Switch
Pole
Function
Operation by switch
Effective
timing
Remarks
ON
OFF
SW11
1s digit
address
setting
SW12
10s digit
address
setting
Rotary switch
0
5
9
4
8
3
7
2
6
1
0
5
9
4
8
3
7
2
6
1
SW12
10
SW11
1
Address setting should be done
when M-NET remote controller
is being used.
Before
power
supply
ON
<Initial setting>
0
5
9
4
8
3
7
2
6
1
0
5
9
4
8
3
7
2
6
1
SW12
SW11
SW14
Connection
No.
setting
Rotary switch
0
8
F
7
E
6
D
5
C
4
B
3
A
2
9
1
SW14
This is the switch to be used
when the indoor unit is operated
with R2 series outdoor unit
as a set.
<Initial setting>
0
8
F
7
E
6
D
5
C
4
B
3
A
2
9
1
SW14
SW21
Function
Selection
1
Setting the ceiling height
Depending on the combination
of SW21-1 and SW21-2.
Refer to <Table E> below.
Under
suspension
<Initial setting>
ON
OFF
1 2 3 4 5 6
2
Setting the ceiling height
3
Setting the number of air outlet
Depending on the combination
of SW21-3 and SW21-4.
Refer to <Table E> below.
4
Setting the number of air outlet
5
Setting for optional parts
Option
Standard
6
Not used
Not used
Not used
PLFY-M20VEM PLFY-M25VEM
PLFY-M32VEM PLFY-M40VEM
PLFY-M50VEM PLFY-M63VEM
PLFY-M80VEM
PLFY-M100VEM PLFY-M125VEM
Silent
Standard
High ceiling
Silent
Standard
High ceiling
SW21-1 SW21-2 SW21-1 SW21-2 SW21-1 SW21-2 SW21-1 SW21-2 SW21-1 SW21-2 SW21-1 SW21-2
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
4 directions
SW21-3 OFF
2.5 m
2.7 m
3.5 m
2.7 m
3.2 m
4.5 m
SW21-4 ON
3 directions
SW21-3 OFF
2.7 m
3.0 m
3.5 m
3.0 m
3.6 m
4.5 m
SW21-4 OFF
2 directions
SW21-3 ON
3.0 m
3.3 m
3.5 m
3.3 m
4.0 m
4.5 m
SW21-4 OFF
Note: The setting with
indicates the initial setting; To change it to other than
, switch setting is necessary.
Blowout directions
Ceiling height
<Table E>
Continue to the next page