VIII
Troubleshooting ]
- 26 -
HWE08010
GB
5. Dipswitch setting (Factory setting)
1. Function
setting
(1) SW1
1) Adress board
(2) SW3
*1 Please don't use SW3-9,10 as trouble might be caused by the usage condition.
1) Indoor control board
Dipswitch settings must be made while the unit is stopped.
Switch position
Function
Switch setting
ON
OFF
1
Active Thermistor (Intake air ther-
mistor)
Built-in thermistor on the remote
controller
Indoor unit
2
Filter clogging detection
Available
Unavailable
3
Filter life
2500 hr
100 hr
4
Outdoor air intake
Enabled
Disabled
5
Remote display
Thermo-ON signal
Fan output
6
Humidifier operation
During heating mode
During heating operation
7
Fan speed
Low
Very low
8
Fan speed at heating Thermo-OFF Preset fan speed
Follows the setting of SW1-7
9
Auto restart after power failure
Enabled
Disabled
10
Power start/stop
Enabled
Disabled
Factory setting
Switch position
Function
Switch setting
ON
OFF
1
Unit type
Cooling only
Heat pump
2
-
-
-
3
-
-
-
4
Heater backup
Enabled
Disabled
5
-
-
-
6
-
-
-
7
-
-
-
8
Sensible temprature correction
Disabled
Enabled
9
Superheat setting tempurature*1
-
-
10
Sub cool setting tempurature*1
-
-
Factory setting
PEFY-P06NMSU-E
PEFY-P15NMSU-E
PEFY-P08NMSU-E
PEFY-P18NMSU-E
PEFY-P12NMSU-E
PEFY-P24NMSU-E