[
VII
Microprocessor Control ]
- 11 -
HWE08010
GB
In the air : Detected that the float switch is OFF for 15 seconds.
2. Dry operation
1. Termoregulating
function
(1) Thermo regulating function (Function to prevent restarting for 3 minutes)
Setting the Dry thermo by the thermo regulating signal and the room temperature (TH21).
Dry thermo ON Room temperature
desired tempe 2°F
Dry thermo OFF Room temperature
desired temperature
(2) Frozen prevention control
No control function
2. Fan
(1) Indoor fan operation controlled depends on the compressor conditions.
<How to operate>
1. Press POWER [ON/OFF] button.
2. Press the operation [Mode] button to display DRY.
3. Press the [Set Temperature] button to set the desired tempera-
ture.
The set temperature changes 2°F when the [Set Temperature]
button is pressed one time. Dry 67 to 87°F
Room temperature
3 min. passed since starting operation
Dry thermo
ON time (min)
Dry thermo
OFF time (min)
Thermo regulating signal
Room temperature (T1)
Over 64°F
ON
T1
83°F
9
3
83°F > T1
79°F
7
3
79°F > T1
75°F
5
3
75°F > T1
3
3
OFF
Unconditional
3
10
Less than 64°F
Dry thermo OFF
Dry thermo
Fan speed notch
ON
[Low]
OFF
Excluding the following
Stop
Room temp. < 64°F
[Low]
ON
OFF
15sec.
15sec.
15sec.
1min.30sec.
1min.30sec.
Float SW
In the water
In the air
In the water
Error
postponement
Drain pump
abnormal
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK
DAY
MONITOR/SET
CLOCK
ON/OFF
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
Summary of Contents for City Multi PEFY-P06NMSU-E
Page 5: ...iv HWE08010 GB ...
Page 7: ...HWE08010 GB ...