VII
Microprocessor Control ]
- 18 -
HWE08010
GB
2) PEFY-P-NMHU-E, PDFY-P-NMU-E and other models
For relay X use the specifications given below Operation coil
Rated voltage: 12VDC
Power consumption: 0.9W or less
* Use the diode that is recommended by the relay manufacturer at both ends of the relay coil.
The length of the electrical wiring for the PAC-YU25HT is 2 meters (6-1/2 ft.)
To extend this length, use sheathed 2-core cable.
Control cable type: CVV, CVS, CPEV or equivalent.
Cable size: 0.5 mm
2
~ 1.25 mm
2
(16 to 22 AWG)
Don't extend the cable more than 10 meters (32ft)
(4) Wiring restrictions
Keep the length of the cable connecting to the circuit board of the indoor unit shorter than 10 meters (32ft).
Longer than 10 meters (32ft) could cause improper operation.
Use a transit relay when extending wiring such as remote wiring.
CN24
CN22
X
X
Remote control board
Relay circuit
Adapter
Indoor unit
control board
Outdoor unit
control board
r
et
a
e
H
cir
t
c
el
E
e
cr
u
o
s
r
e
w
o
p
Red
1
White
2
• PUHY, PURY-P-
TGMU type Dip
switch SW5-2
“ON”
• PUHY, PURY-P-
YHMU type Dip
switch SW5-10
“ON”
• PUMY series Dip
switch SW4-4
“ON”
Preparations in the field
Maximum cable length
is 10 m (32ft)
w
oll
e
Y
n
e
er
G
White
1
Dip switch SW3-2 “ON”
(applicable only when a panel
heater is connected)
2
Electric Heater
or panel
heater
Recommended circuit
Wiring diagram
1-phase power
supply
208V, 230V/60Hz
Control board
FS1, 2 ----- Thermal fuse
H1, H2 ----- Heater
26H --------- Overheat protection
thermostat
88H --------- Electromagnetic contactor
FS1
FS2
FS1
FS2
R
S
R
S
CN24
H2
88H
H1
88H
26H
88H
Summary of Contents for City Multi PEFY-P06NMSU-E