2
2
2.2
2.3
2.4
[Fig. 2.4.1]
[Fig. 2.4.2]
[Fig. 2.2.1]
450□
450□
A
A
Service space
Indoor unit side
(700)
B
B
300
250
A
100
120
200
F
D
C
Service space
F
G
Service space
F
Service space
F
B
E
<B>
<A>
[Fig. 2.3.1]
<A> Top view
<B> Front view
Model name
A
B
CMB-WP108V-GA1
1520
160
CMB-WP1016V-GA1
1800
300
CMB-WP108V-GB1
1520
160
CMB-WP1016V-GB1
1520
160
*1 Dimensions with which pipe connection can be handled at site
A
Inspection hole
B
Side of outdoor unit piping
C
Control box
D
Side of indoor unit piping
E
Water inlet
F
Service space
G
Indoor unit side
D
D
D
D
J
D
A
B
I
G
K
L
C
H
F
E
A
c
d
e
b
a
h1
h2
f
g
HH
1
A
Outdoor unit
B
Main-HBC controller
C
Sub-HBC controller
D
Indoor unit
E
Less than H=50 m (when the outdoor unit is higher than HBC)
F
Less than H1=40 m (when the outdoor unit is lower than HBC)
G
Twinning pipe (field supply)
H
Less than 110 m
I
Less than 60 m
J
Up to three units for 1 branch port
Total capacity: less than 80 (but in same mode, cooling/heating)
K
Less than 15 m
L
Less than 15 m
CMB-WP108V-GA1 + CMB-WP108V-GB1
(CMB-WP1016V-GA1) (CMB-WP1016V-GB1)
Notes:
*1 Indoor units that are connected to the same branch joint cannot be si-
multaneously operated in different operation modes.
(Unit: m)
Item
Piping portion
Allowable value
Between outdoor unit and
HBC controller (refrigerant pipework)
A
110 or less
Water pipework between indoor units
and HBC controller
f + g
60 or less
Between
indoor and
outdoor units
Above outdoor unit
H
50 or less
Below outdoor unit
H1
40 or less
Between indoor units and HBC controller
h1
15 or less
Between indoor units
h2
15 or less
Pipe L
engt
hs
D
iff
er
en
ce
of
el
ev
at
io
n
C
J
D
A
B
B
H
I
G
K
L
D
D
D
D
M
D
F
E
G
A
c
d
e
f
b
a
h1
h2
g
h3
HH
1
B
A
Outdoor unit
B
Main-HBC controller
C
Sub-HBC controller
D
Indoor unit
E
Less than H=50 m (when the outdoor unit is higher than the indoor unit)
F
Less than H1=40 m (when the outdoor unit is lower than the indoor unit)
G
Twinning pipe (field supply)
H
Less than 110 m
I
Less than 60 m
J
Up to three units for 1 branch port
Total capacity: less than 80 (but in same mode, cooling/heating)
K
Less than 15 m
L
Less than 15 m
M
Less than 15 m
CMB-WP108V-GA1 + CMB-WP108V-GB1
(CMB-WP1016V-GA1) (CMB-WP1016V-GB1)
(Unit: m)
Item
Piping portion
Allowable value
Between outdoor unit and
HBC controller (refrigerant pipework)
A
110 or less
Water pipework between indoor units
and HBC controller
f + g
60 or less
Between HBC controllers
B
40 or less
Between
indoor and
outdoor units
Above outdoor unit
H
50 or less
Below outdoor unit
H1
40 or less
Between indoor units and HBC controller
h1
15 or less
Between indoor units
h2
15 or less
Between HBC controllers
h3
15 or less
P
ipe L
engt
hs
Dif
feren
ce o
f ele
vati
on