(5)
LEV
Be careful on removing heavy parts.
Procedure
Photos
1. Remove the service panel. See (1)-1.2.3
2. Replace the applicable LEV.
Important!
1
When performing the above procedure, be sure to
allow for enough service space in the ceiling area
for welding.
2
When conditions require, the unit can be lowered
from the ceiling before starting work.
(6)
Solenoid Valve Coil
Procedure
Photos
1. Remove the service panel. See (1)-1.2.3
2. Disconnect the connector of the applicable
solenoid valve.
3. Remove the solenoid valve coil.
1
SVA, SVB solenoid valve coils can be serviced
from the maintenance port.
SVC can serviced from the back if service
space is available in the back. To remove the
back panel, remove the four screws that
secure it.
Solenoid valve
LEV3
LEV1
- 117 -