- 180 -
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
Start
Test run all indoor units.
Is the refrigerant
composition of OC
correct? (Note 2)
Finished checking the
composition.
Check TH2, LPS and the CS
circuit block and correct any malfunc-
tions. (Note 3)
Is the
refrigerant composi-
tion of OC correct?
(Note 2)
Finished checking the
composition.
Check that
R407C is correctly
charged.
(Note 4)
Recharge the refrigerant.
(Note 5)
Finished checking the
composition.
Calibrate the refrigerant composition
of OC
. (Note 6)
Are all units operating
stably? (Note 1)
CHECK THE COMPOSITION OF THE REFRIGERANT(R407C unit only)