MITSUBISHI ELECTRIC 9800A SERIES UPS
MITSUBISHI
ELECTRIC
9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-5
TABLE 3.4
Recommended Cable Sizes
Input Side
* 1, 2
Output Side
* 1, 2
Bypass Side
* 1, 2
DC Input Side
* 1, 2
kVA
Capacity
Input
Voltage
Output
Voltage
Cable
Size
Torque
in. lbs
Cable
Size
Torque
in. lbs
Cable
Size
Torque
in. lbs
Cable
Size
Torque
in. lbs
100kVA
480V
480V
1 AWG
or larger
100 - 135
in. lbs
1 AWG
or larger
100 - 135
in. lbs
1 AWG
or larger
100 - 135
in. lbs
3/0 AWG
or larger
100 - 135
in. lbs
600V
600V
2 AWG
or larger
100 - 135
in. lbs
2 AWG
or larger
100 - 135
in. lbs
2 AWG
or larger
100 - 135
in. lbs
3/0 AWG
or larger
100 - 135
in. lbs
150kVA
480V
480V
3/0 AWG
or larger
100 - 135
in. lbs
3/0 AWG
or larger
100 - 135
in. lbs
3/0 AWG
or larger
100 - 135
in. lbs
350 MCM
or larger
100 - 135
in. lbs
600V
600V
2/0 AWG
or larger
100 - 135
in. lbs
2/0 AWG
or larger
100 - 135
in. lbs
2/0 AWG
or larger
100 - 135
in. lbs
350 MCM
or larger
100 - 135
in. lbs
225kVA
480V
480V
300 MCM
or larger
100 - 135
in. lbs
350 MCM
or larger
100 - 135
in. lbs
350 MCM
or larger
100 - 135
in. lbs
2x4/0 AWG
or larger
100 - 135
in. lbs
600V
600V
250 MCM
or larger
100 - 135
in. lbs
250 MCM
or larger
100 - 135
in. lbs
250 MCM
or larger
100 - 135
in. lbs
2x4/0 AWG
or larger
100 - 135
in. lbs
300kVA
480V
480V
2x4/0 AWG
or larger
347 - 469
in. lbs
2x3/0 AWG
or larger
347 - 469
in. lbs
2x3/0 AWG
or larger
347 - 469
in. lbs
2x400 MCM
or larger
347 - 469
in. lbs
600V
600V
2x3/0 AWG
or larger
347 - 469
in. lbs
400 MCM
or larger
347 - 469
in. lbs
400 MCM
or larger
347 - 469
in. lbs
2x400 MCM
or larger
347 - 469
in. lbs
375kVA
480V
480V
3x300 MCM
or larger
347 - 469
in. lbs
2x250 MCM
or larger
347 - 469
in. lbs
2x250 MCM
or larger
347 - 469
in. lbs
3x350 MCM
or larger
347 - 469
in. lbs
600V
600V
2x4/0 AWG
or larger
347 - 469
in. lbs
2x3/0 AWG
or larger
347 - 469
in. lbs
2x3/0 AWG
or larger
347 - 469
in. lbs
3x350 MCM
or larger
347 - 469
in. lbs
500kVA
480V
480V
3x250 MCM
or larger
347 - 469
in. lbs
2x400 MCM
or larger
347 - 469
in. lbs
2x400 MCM
or larger
347 - 469
in. lbs
3x500 MCM
or larger
347 - 469
in. lbs
600V
600V
2x350 MCM
or larger
347 – 469
in. lbs
2x300 MCM
or larger
347 - 469
in. lbs
2x300 MCM
or larger
347 - 469
in. lbs
3x500 MCM
or larger
347 - 469
in. lbs
750kVA
480V
480V
3x500 MCM
or larger
347 - 469
in. lbs
3x500 MCM
or larger
347 - 469
in. lbs
3x500 MCM
or larger
347 - 469
in. lbs
5x500 MCM
or larger
347 - 469
in. lbs
600V
600V
3x350 MCM
or larger
347 - 469
in. lbs
3x350 MCM
or larger
347 - 469
in. lbs
3x350 MCM
or larger
347 - 469
in. lbs
5x500 MCM
or larger
347 - 469
in. lbs
*1 - The cables must be selected to be equal to or larger than the sizes listed in the table.
*2 - Voltage drop across power cables not to exceed 2% of nominal source voltage.
*3 - Allowable ampere-capacities based on 90 degree C insulation at ambient temperature of 30 degree C.
Not more than 3 conductors in a raceway without de-rating.
Note: Copper conductors assumed.