MITSUBISHI ELECTRIC 9800A SERIES UPS
MITSUBISHI
ELECTRIC
9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-17
TABLE 1.6
Rating of Contactors and Fuses
OUTPUT CAPACITY OF EQUIPMENT
100kVA
150kVA
225kVA
300kVA
375kVA
500kVA
750kVA
NUMBER
APPLICATION
480V
600V
480V
600V
480V
600V
480V
600V
480V
600V
480V
600V
480V
600V
CB1
AC input contactor
135A
200A
350A
450A
660A
660A
910A
CB2
Battery disconnect
breaker
225A
350A
500A
700A
900A
1200A
2000A
CB3
STS contactor
135A
260A
52C
Inverter output
contactor
135A
200A
350A
450A
450A
660A
910A
52S
Bypass contactor
135A
200A
350A
450A
450A
660A
910A
C
o
n
ta
c
to
r,
B
re
a
k
e
r
88RC
Control circuit contactor
90A
FCU, FCV, FCW
AC input fuse
200A-690V
250A-690V
315A-690V
FDU,FDV,FDW
FDX,FDY,FDZ
FDP,FDN
DC arm fuse
450A-690V
450A-690V
630A-690V
900A-550V
900A-550V
630A-690V
900A-550V
FUA, FUB, FUC
Control power fuse
30A-600V
(OPTION)
FSU, FSV, FSW
Bypass input fuse
200A-
690V
-
315A-
690V
-
250A-
690V
-
250A-
690V
-
315A-
690V
-
315A-
690V
-
315A-
690V
-
FZS1, 2, 3
Bypass input ZNR fuse
5A- 500V
FBS1, 2, 3
Control power fuse
10A-600V
FZR1, 2, 3
AC input ZNR fuse
5A- 500V
F
u
s
e
s
FPU, FPV, FPW
Parallel control
circuit fuse
3A- 600V
*Rating would be changed.