MITSUBISHI ELECTRIC 9800A SERIES UPS
MITSUBISHI
ELECTRIC
9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-16
TABLE 1.5
Detail of Specifications
Rated Output kVA
100
150
225
300
375
500
750
Rated Output kW
80
120
180
270
338
450
675
AC INPUT
Configuration
3 phase, 3 wire
Voltage
277/480 V, 346/600 V
+15% to -15%
Frequency
60 Hz +/-5%
Reflected Current THD
6% max. at 100% load;
9% max. at 50% load
STATIC BYPASS INPUT
Configuration
3 phase, 4 wire
Voltage
277/480 V, 346/600 V
+/-10%
Frequency
60 Hz
BATTERY
Type
Lead Acid
Ride Through
Application Specific
Nominal Voltage
480 Vdc
Minimum Voltage
400 Vdc
Number of Cells
240
AC OUTPUT
Configuration
3 phase, 4 wire
Voltage
277/480 V, 346/600 V
Voltage Stability
+/-
1%
Frequency
60 Hz
Frequency Stability
+/-
0.05% in free running mode
Power Factor
0.8 nominal
0.9 nominal
Power Factor range
0.8 to 1.0 lagging (within output kW rating)
Voltage THD
2% maximum THD at 100% Linear Load
5% maximum THD at 100% non-linear load
Transient Response
+/-
2% maximum at 100% load step
+/-
1% maximum at loss/return of AC power
+/-
5% maximum at load transfer to/from static bypass
Transient Recovery
Less than 20ms
Voltage Unbalance
1% maximum at 100% unbalanced load
Phase Displacement
1deg. maximum at 100% load
Inverter Overload
125% for 10 minutes; 150% for 1 minute
System Overload
1000% for 1 cycle
(with bypass available)
500% for 1 cycle
(with bypass available)
Bypass Overload
125% for 10 minutes
Withstand Rating
65kA*
* : with optional fuse
ENVIRONMENTAL
Cooling
Forced Air
Operating Temperature
32
゚
F to 104
゚
F ( 0
゚
C to 40
゚
C).
Recommended : 68
゚
F to 86
゚
F ( 20
゚
C to 30
゚
C)
Relative Humidity
5% ~ 95% Non Condensing
Altitude
0 to 9000 feet No Derating
Location
Indoor (free from corrosive gases and dust)
Paint Color
Munsell 5Y7/1 (Beige)