98
QAS-2X8 Splitter Configuration - QX-mini and FX-3500 - Two Stage
In this example, there is an evacuation message set to “Evacuation Stage” and an alert
message set to “Alert Stage”.
Figure 140 Audio Clips
3.
Click “Close” to close the Audio window.
Assign Zones and Messages to Inputs
1.
Click “Panel Inputs”.
Figure 141 Panel Inputs button
The SLC/RELAY-IN/SYNC Correlations window appears (Figure 142).
2.
Click the “+” button. Select the panel input addresses to activate the evacuation and alert
zones. Ensure that the addresses correspond to the modules in the FACP configuration.
An example configuration is shown in Table 3. The addresses in Table 3 correspond to
the addresses on the FX-3500 shown in Table 1.
3.
Use the arrows to move the evacuation zones above the alert zones so that the
evacuation zones have higher priority.
Note:
In this example, CLIP modules range from 201 to 299 on the FX-3500.
On the QX-mini they range from 101 to 199.