SLC Integration - QX-mini and FX-3500 - Single Stage
57
became 201-299 in the configurator as shown in Figure 81.
Figure 83 Configure all the reporting addresses corresponding to addresses on
FACP.
Note:
Under signal silence, three different behavior options can be selected:
All, Speakers, Horn & Strobes. “All” turns off all the outputs,
“Speakers” turns off speaker outputs only, and “Horn & Strobes” turns
off NACs when signal silence on FACP is pressed.
9.
If NACs on FACP need to be in sync with NACs on QX-mini, select appropriate stage,
strobe protocol, and select “Follow Sync Input”.
10.
Create a zone for EVAC. Correlate the NACs and amplifier outputs to that zone and
assign an audio message.
Figure 84 Create zones