58
SLC Integration - QX-mini and FX-3500 - Single Stage
11.
Click on panel inputs, click on the ‘+’ sign. Select Panel input address to activate EVAC
zone. Ensure this address corresponds to “supervised output module” in Figure 81.
Figure 85 SLC/RELAY-IN/SYNC Correlations
12.
All the correlations in job file can be viewed in “Report” as shown below.
Figure 86 Report
13.
Save the job, connect to QX-mini Master and send the job.
14.
After job has been successfully sent to the panel, disconnect the USB connector.