SLC Integration - QX-mini and FleX-Net™ - Two Stage
14.
In order to see “Page Inhibit” countdown, the feature can be assigned to one of the zone
switches. Right click on the switch and select “Assign paging inhibit”. Flashing of the
LED will indicate countdown of the inhibit.
15.
All the correlations in job file can be viewed in “Report” as shown below.
Figure 39 Report
16.
Save the job, connect to QX-mini and send the job.
17.
After job has been successfully sent to the panel, disconnect the USB connector.
4.4
SLC Address Configuration
•
Alarm Input
: In Figure 32 on page 22, Input Module address 101 is an example of any
alarm input in the job. It would need to be correlated to the Supervised Output module
addresses to activate the Alert zone on QX-mini.
•
Common Trouble
: This feature allows the QX-mini to report any trouble(s) back to the
FACP. Referring to Figure 32, address 103 is an example of trouble input. Configure the
type as “trouble input” in the FACP configurator.
•
Signal Silence
: This feature allows FACP to silence audible and visible devices on the
QX-mini.
• Audible and Visual signal silence: Configure this as a relay output module, address
104 (shown in Figure 32), and correlate it to “signal silence” common status in the
FACP configurator.
•
Paging/Message Active
: This feature reports to FACP when QX-mini has been
manually activated. For example, when microphone is active or a message has been
activated, trouble will report back to FACP. Configure this as an input module (Address
105 in Figure 32) in the FACP configurator, and select type as “building/property safety”.
•
AC Trouble
: This feature reports QX-mini AC failure to FACP. If QX-mini is configured
for “AC Loss Delay” then a trouble will only be reported after the delay. Configure this as
an input module (Address 106 in Figure 32), and select type as “trouble input” in the
FACP configurator.
•
Battery/Charger Trouble
: This feature reports to FACP when QX-mini has a battery or
battery charger trouble. Configure this as an input module (Address 107 in Figure 32),
and select type as “trouble input” in the FACP configurator as shown in Figure 32.
•
Earth Ground Fault
: This feature reports to FACP when there is a ground fault detected
on QX-mini system. Configure this as an input module (Address 108 in Figure 32) and
select type as “trouble input” in the FACP configurator.