80
TNC-5000 Telephone Network Controller Module
Figure 62 QAZT-5348DS Network Firefighters' Telephone Selector Panel
Each QAZT-5348DS annunciates and controls up to 48 telephone zones. There is one button
and two LEDs per zone. The lower amber LED indicates zone trouble. The upper green LED
indicates whether that zone is selected for telephone communication.
Telephone zone selection buttons toggle ON and OFF telephone communication for that zone.
9.8
QAZT-5348DS Network Firefighters’ Telephone Selector Panel
Connect the first QAZT-5348DS Network Firefighters’ Telephone Selector panel to the master
telephone by connecting the Ribbon In cable into P2 on the QMT-5302NV Master Telephone.
Ribbon Out cable to the Ribbon In of the next QAZT-5348DS or P1 of the next display panel
(up to six total). See Figure 63 below.
Note:
Use configurator to set up the QAZT-5348DS Telephone Zone Selector Panels
.
Note:
All modules such as QMP-6101NV Network Master Paging Control Module, the
QMT-5302NV Network Master Firefighters’ Telephone Control Module, the IPS-
4848DS display module and the paging or telephone selector panel QAZT-
5348DS are daisy chained together starting from the LCD display module, DSPL-
420DS, DSPL-2440, RAXN-LCD or RAXN-LCDG. Total number of boards allowed in
the daisy chain connection is 6 (12 frames).
i
i