107
Appendix A: Specifications
DSPL-420DS and DSPL-2440 Displays
Programmable Input Switches Module (IPS-2424DS)
Current Consumption:
standby:
25mA and 35mA
alarm:
25mA and 30mA
Current Consumption:
standby: 5 mA
alarm (one zone active): 22 mA
Fan Damper Display Module (FDX-008W/KI)
Programmable Input Switches Module (IPS-4848DS)
24V DC nominal, range of 20 to 39V DC.
Current Consumption:
standby: 15mA Max.
alarm (all LEDs ON): 35mA Max.
Current Consumption:
standby: 10 mA
alarm (one zone active): 22 mA
Digital Communicator Module (UDACT-300A)
Adder Annunciator Module RAX-1048TZDS
Transmit alarm, supervisory, and trouble to a central monitoring
station.
Current Consumption:
standby: 45
mA
alarm: 120
mA
48 Display Points
Current Consumption:
standby: 139 mA
alarm: 1 zone LED active: 26 mA
2 zone LEDs active: 30 mA
3 zone LEDs active: 35 mA
4 zone LEDs active: 39 mA
48 zone LEDs active: 262 mA
Compliance
System Model:
FX-6000MNS-CH
System Type:
Local, auxiliary (using PR-300), remote protected premise station (using PR-300 or
UDACT-300A), central station protected premises (using UDACT-300A).
Proprietary Sytem (PPU)
and Smoke Control
Type of Service:
A, M, WF, SS (with PR-300 or UDACT-300A), PPU
Type of Signalling:
Non-coded
Applicable Standards:
NFPA 70 and 72, UL-864 R10, ULC S-524, ULC S527-11