22
Figure 10 Main Fire Alarm Module (MD-871A”N” Version Main Board.
4.1.1 SW2 DIP Switch Node Address Setting on Main Fire Alarm Module
Refer to table in Appendix for Node Address Setting. Available addresses are 1 to 63. DIP
Switch SW2-1 is the least significant digit.
4.2
DSPL-420DS Main Display Module
The DSPL-420DS mounts onto inner door of the BBX-FXMNS-6000. This display is part of the
following main fire alarm chassis: FX-6000MNS-CH.
Figure 11 DSPL-420 Main Display Module (Part of Main Chassis c/w Main Fire Alarm
Module)
P1:
Cable connects to P14 of the main fire alarm board (Figure 10).
P2:
Connection to P1 of any adder display module if used.
Note:
The main display module comes with slide-in paper labels including both English
and French slide-ins, and laser printer-compatible blanks for zone labelling.
F1
MAIN FIRE ALARM BOARD
FIELD WIRING TERMINALS
P3
P2 P1
P16
P10 P11
P15
P4
J1
P9
P7
P5
P6
P8
+ BR - +BAT -
NAC PWR
P14
P19
JW1
JW4
JW5
JW6
JW2
SW2
1
8
ON
i