This document provides information for the successful installation and operation of the FX-
3318 and FX-3318-NG.
2.1 The FX-3318 Series Addressable Fire Alarm Control Panels
Mircom’s FX-3318 Series Addressable Fire Alarm Control Panel provides the following:
•
Advanced Protocol mode with one loop with 159 addressable sensors and 159
addressable modules per loop.
•
CLIP Device compatible.
•
Four Power Limited Class B (Style Y) or Class A (Style Z) NAC circuits.
•
NAC circuits may be configured as silenceable signal, non-silenceable signal,
silenceable strobes, non-silenceable strobes, or relay output. The audible signal may be
Steady, Temporal Code, California Code, or March Time.
•
Supports sync strobe protocols from major manufacturers.
•
Software configuration.
•
Two-stage, alarm verification, waterflow retard and positive alarm sequence operations.
•
Configurable Signal Silence Inhibit, Auto Signal Silence, and One-Man Walk Test.
•
Subsequent Alarm, Supervisory, Monitor and Trouble operation.
•
Relay Contacts for Common Alarm, Common Supervisory and Common Trouble all
non-disconnectable and Auxiliary Alarm Relay (disconnectable).
•
Built-in Dialer Module.
2.1.1 Optional Items
•