Operation
subaddress, “Parm#” indicates parameter number from the current subaddress, and “Val#”
indicates the paramter value.
5.10.4 Clear Logs
Clears the logs stored in the flash memory. Use the
UP
and
DOWN
cursor keys to the desired
log to be cleared and press the
Enter
button.
A message prompts for confirmation.
After confirmation the logs are cleared and the following information message is displayed:
5.10.5 Walk Test
Initiates a silent or audible Walk Test. The following occurs when in Walk Test mode:
•
Generates a non-latching trouble that clears after exiting the walktest.
•
Cancelling the walk test is done by pressing the
Cancel
button or if no circuit activations
are detected for one hour.
•
Zone indicators, including the Smart Relay Module (SRM-312) function normally during
the test, displaying the input status when it is activated.
•
Other Relays and signal correlations to input circuits are not processed during walk-test.
Correlations to system status will still be processed.
•
All common controls and keys not explicitly required for the walk-test operation are
disabled while the walk-test is active.
•
The alarm verification and waterflow retard operation is disabled on inputs during walk-
test.
During an Audible walk test:
•
activating any input activates all signals for half a second.
•
Trouble on any input activates all signals continuously for 5 seconds. After the code is
transmitted, the input resets (if resettable) and is tested again. If it is still in alarm or
trouble the code will be re-transmitted.
Use the
UP
and
DOWN
cursor keys to scroll to the desired option press the
Enter
button.
Crt. S/A Parm# Val
1 000 01 002
2 000 02 034
3 000 02 003
Select Log
1. Alarm Log
2. General Log
3. All Logs
Clear all the
Selected log (s)?Y/N
Log(s) cleared